Operation Mode Behavior

The control panel can be in one of seven conditions at any given moment: Normal, Alarm,
Prealarm, Supervisory, Trouble, Silenced, and Reset. Table 8-1 describes the behavior of the
panel in each of these modes.
Operation
Occurs When
Mode
Normal
No alarm or
trouble
condition exists
and menus are
not in use.
Alarm
A smoke
detector goes
into alarm or a
pull station is
activated.
151209
Table 8-1: Operation Mode Behavior
System Behavior
SYSTEM POWER LED is on.
The All Systems Normal display indicates
that the system is in normal mode.
The current date and time display on the
last line of the LCD.
The dialer seizes control of the phone line
and calls the central station.
The on-board annunciator sounds a loud,
steady beep (any notification devices
attached to the system will also sound).
GENERAL ALARM LED flashes.
The LCD displays a screen similar to this
one.
firealarmresources.com
System Operation
In This Mode You Can
Enter the appropriate code to activate the User or
Installer Menu, or rotate the key to activate the User
Menu.
Press the down arrow to view the alarm. A screen
similar to this one displays.
SILENCE
Press
and enter an access code (or
activate the key) to silence the annunciator (and any
notification devices attached to the system).
When the alarm condition clears, press
and enter a code (or activate the key) to restore the
panel to normal.
RESET
8-11