Answering Machine Bypass; Sys. Event Outputs - Honeywell Silent Knight IntelliKnight 5820XL Installation And Operation Manual

Addressable fire system
Table of Contents

Advertisement

disabled by default. For 5211 installation, see Section 4.12.
Note: Ground start cannot be used in UL installations.
12. Select Y (ground start used monitor line) or N (ground start not used don't monitor line)
by pressing the

7.6.2.7 Answering Machine Bypass

This option is used in conjunction with the 5660 SKSS. This feature ensures that an answering
machine will not interfere with communication between the panel and the computer. If an
answering machine is used at the panel site, enable this feature; if an answering machine is not
used, disable the feature.
This option is factory-programmed as Yes (enabled).
The selection made here must match the programming for this option in the Communication
Configuration dialog box of the 5660 SKSS. See the 5660 SKSS manual for more information
(PN 151240).
13. Select Y (answering machine bypass enabled) or N (answering machine bypass disabled)
by pressing the
7.6.3

Sys. Event Outputs

1. Enter the installer code.
2. Press
to display the main menu.
or
3. Select
for Program Menu.
7
Display reads:
4. From the Program Menu, select
5. From the System Options Menu, select
151209
or
arrow, then press
or
arrow, then press
Initializing
Please wait . . .
for System Options.
5
for Sys. Event Outputs.
2
firealarmresources.com
.
.
Programming
7-35