Honeywell Silent Knight IntelliKnight 5820XL Installation And Operation Manual page 41

Addressable fire system
Table of Contents

Advertisement

3. Run extended battery cable from control panel cabinet through conduit to RBB cabinet.
See Figure 4-5.
Conduit
Coupler
Conduit
Figure 4-5 Battery Connections in the RBB Cabinet
Note: Figure 4-5 is an example of how the wire connections can be routed. However, any other cabinet knock-
outs (on either the main control panel or the RBB cabinet), that are not previously being used may be uti-
lized to connect conduit between the two cabinets.
4. Connect battery leads to the backup battery terminals. See Figure 4-5.
Observe the proper polarity to prevent damage to the batteries or the control panel.
5. Insert the RBB cover screws into the cover mounting holes (see Figure 4-5).
Screw the cover screw 3/4 of the way into the cover mounting hole.
6. Align the cover plate mounting keyhole over the cover mounting screws. See Figure 4-6.
Figure 4-6 Cover Plate Mounting Keyholes and Cover Mounting Screws Alignment
7. Slide the cover into place and tighten the cover mounting screws. See Figure 4-6
151209
RBB Cabinet
Cover Screws
-
+
RBB Cabinet
Cover Screws
Cover Plate
Mounting Keyholes
firealarmresources.com
Control Panel Installation
-
+
4-5

Advertisement