Honeywell Silent Knight IntelliKnight 5820XL Installation And Operation Manual page 136

Addressable fire system
Table of Contents

Advertisement

IntelliKnight 5820XL Installation Manual
Table 7-5: Point Programming Options for 5815XL Modules
Type
Function
Selection
ZN_AUX1
ZN_AUX2
SYS_AUX1
SYS_AUX2
SWITCH
(cont.)
DETECT SW
TAMPER
MAN REL
ILOCK
OUTPUT PT
AUX CONST
NOTIF
AUX RESET
AUX DOOR
OUTPUT PT
AUX RESET
RELAY
AUX DOOR
7-22
Latching
Option
Latching
Use these switch types if you want to monitor special zone-level conditions
(such as operation of a fan or damper).
Non Latching
Latching
Non Latching
Latching
Use these switch types if you want to monitor special system-wide
conditions (such as operation of a fan or damper).
Non Latching
Latching
Non Latching
Used to monitor conventional 4-wire detectors, a contact closure will
generate a detector alarm event.
Latching
Performs identically to a supervisory switch, but will be indicated as a
tamper switch on the LCD annunciator.
Non Latching
Latching
Manual release switch, typically a pull station.
Non Latching
Latching
Interlock release switch input.
Non Latching
Output Point, a general use notification type. Use for driving standard
Select Group
notification appliances.
Use constant power for applications that require a constant auxiliary power
source. Power is always present at Constant circuits.
Use for auxiliary power, resettable applications. See Section 4.13.5.3 for a
description of how this option operates.
Use for auxiliary power, door holder applications. For example, if you were
using an auxiliary power supply for door holders, you would use this option.
See Section 4.13.5.1 for a description of how this option operates.
Output Point, a general use relay type. Use for applications requiring a relay,
Select Group
such as fan shutdown, elevator recall, and so on.
Use for auxiliary power, resettable applications. See Section 4.13.5.3 for a
Select Group
description of how this option operates.
Use for auxiliary power, door holder applications. For example, if you were
Select Group
using an auxiliary power supply for door holders, you would use this option.
See Section 4.13.5.1 for a description of how this option operates.