Rectifier Nominal 120 Vac / 208 Vac / 240 Vac Input And Ac Input Equipment Grounding Connections - Vertiv NetSure-48 VDC Installation And User Manual

Bulk output rectifier system
Hide thumbs Also See for NetSure-48 VDC:
Table of Contents

Advertisement

WARNING! The intra-building port(s) of the equipment or subassembly is suitable for connection to intra-building or
unexposed wiring or cabling only. The intra-building port(s) of the equipment or subassembly MUST NOT be metallically
connected to the interfaces that connect to the OSP or its wiring. These interfaces are designed for use as intra-building
interfaces only (Type 2 or Type 4 ports as described in GR-1089-CORE, Issue 4) and require isolation from the exposed OSP
cabling. The addition of Primary Protectors is not sufficient protection in order to connect these interfaces metallically to
OSP wiring.
The intra-building port (RJ-45) of the equipment or subassembly must use shielded intra-building cabling/wiring that is
grounded at both ends.
Figure 7.2 NCU Ethernet Port
Table 7.1 NCU RJ-45 Ethernet Port Pin Configuration
Port Pin Number
Name
1
2
3
4
5
6
7
8
7.5 Rectifier Nominal 120 VAC / 208 VAC / 240 VAC Input and AC Input
Equipment Grounding Connections
DANGER! Adhere to the "Important Safety Instructions" presented at the front of this document.
General
The system is equipped with plug-in AC input connectors located on the rear of the system. Mating connectors and cable assemblies
or line cords are available (see "Rectifier AC Input Cable Assemblies and Rectifier AC Input Line Cords" on page 5).
Each 58870530036 Rectifier System requires two (2) AC input cable assemblies or line cords. Each feeds two (2) rectifiers.
Refer to Table 7.2 for recommended AC input branch circuit protection when using the supplied rectifier AC input cable assemblies.
Refer to Table 7.3 for recommended AC input branch circuit protection when using the supplied rectifier AC input line cords.
Refer to Figure 7.3 for an illustration.
Definition
Tx+
Write Signal +
Tx-
Write Signal -
Rx+
Read Signal +
--
no connection
--
no connection
Rx-
Read Signal -
--
no connection
--
no connection
Proprietary and Confidential © 2022 Vertiv Group Corp.
Vertiv™ NetSure™ -48 VDC Bulk Output Rectifier System Installation and User Manual
13