Vertiv™ NetSure™ IPE Series Outdoor Rectifier Installation and User Manual
4.6 Nominal 120 VAC / 220 VAC / 240 VAC Input Power and AC Input
Equipment Grounding Connections
ALERT! AC input power must be turned off before connecting or disconnecting the AC input plug-in connector.
The rectifier is equipped with a plug-in AC input power connector located on the bottom of the enclosure. See Figure 4.1 for location.
A separately ordered AC input power cable assembly with a mating plug is required (refer to Figure 4.4). See also "Pre-Assembled
Cables" on page 2.
This rectifier requires an external AC input branch circuit protective device rated for 15 A.
-
Assuming 208 VAC or 240 VAC Nominal Input: 15 A, 2-pole.
-
Assuming 120 VAC Nominal Input: 15 A, 1-pole (120 VAC results in reduced power output).
Procedure
1.
Connect the separately ordered AC input power cable assembly to the AC input power source as shown in Figure 4.4.
Connect the green lead to Ground. Connect the white lead to Neutral. Connect the black lead to Line.
Figure 4.4 Mating AC Input Power Cable Assembly P/N 10023461 and P/N 10024814 (AC Input Power Connector)
48
P/N 10023461 (32.8 feet)
P/N 10024814 (16.4 feet)
Proprietary and Confidential © 2022 Vertiv Group Corp.