Rectifier Nominal 120 VAC / 208 VAC / 240 VAC Input and AC Input Equipment
Grounding Connections
DANGER! Adhere to the "Important Safety Instructions" starting on page 7, especially "AC Input
Voltages" on page 7.

General

List 01 may be equipped with...
• rear IEC receptacles for connection of AC input line cords (one AC feed per rectifier position),
• pre-wired AC input when factory installed in a Vertiv OSP cabinet (one AC feed per rectifier position), or
• pre-wired AC input with a single AC input line cord or AC input cable assembly (one AC feed per shelf).

AC Input Connections to Rear AC Input IEC Receptacles, if furnished

Each List 01 shelf, when equipped with rear IEC receptacles, requires three (3) AC input line cords. Each feeds
one (1) rectifier position. Refer to SAG582138000 for AC input line cord options and recommended branch
circuit protection.
Procedure
1.
Plug the mating end of the AC input line cords into the IEC AC input receptacles located on the rear of
the shelf. Refer to Figure 26.
2.
Plug the other end of the AC input line cords into a properly wired AC outlet. Refer to Figure 26.
AC Input Connections When System is Pre-Wired in a Vertiv OSP Cabinet
When the system is pre-wired into a Vertiv OSP cabinet, refer to the cabinet documentation for rectifier AC
input wiring.

AC Input Connections when Single AC Input Line Cord or AC Input Cable Assembly is Factory Installed

Refer to the following procedure if a single AC input line cord or AC input cable assembly is factory installed.
This AC input line cord or AC input cable assembly feeds all rectifier positions in the shelf. Refer to
SAG582138000 for AC input line cord and AC input cable assembly options and recommended branch circuit
protection.
Procedure
1.
Connect the dedicated end of the AC input line cord or AC input cable assembly into a properly wired
AC outlet or distribution box. Refer to Figure 27.