1 Customer Documentation Package
This document provides Installation and User Instructions for Vertiv™ NetSure™ -48 VDC bulk output rectifier system Model PSS4840
3/19C, Spec. No. 58870530036.
The complete Customer Documentation Package consists of...
System Installation and User Manual
•
Installation and User Instructions: UM58870530036
Controller User Manual
•
NCU Controller User Instructions: UM1M830BNA
USB Drive with All Customer Documentation
•
Power System Installation and User Instructions: UM58870530036
•
NCU Controller User Instructions: UM1M830BNA
•
Rectifier Instructions: UM1R482000e3
•
Engineering Drawings
•
Also provided on the USB drive is a Controller Configuration Drawing (C-drawing) and the controller configuration files
loaded into the controller as shipped.
For factory settings of all configurable controller parameters, refer to the Configuration Drawing (C-drawing) supplied with your bulk
output rectifier system.
2 System Description
-48 VDC @ Bulk Output Rectifier System
The Vertiv™ NetSure™ PSS4840 3/19C is a bulk output rectifier
system containing a 1RU high by 19" wide shelf with a system
controller mounting slot and four (4) rectifier module mounting
slots.
This bulk output rectifier system is designed to power a load.
This bulk output rectifier system is capable of operating in a
batteryless installation. The bulk output rectifier system is
designed for operation with the positive output grounded.
The bulk output rectifier system consists of the following components.
Controller
NCU (NetSure Control Unit): The controller provides bulk output rectifier system control, rectifier control (including a charge control
function), metering functions, monitoring functions, and local/remote alarm functions. The controller also provides data acquisition,
system alarm management, and advanced battery and energy management. The controller contains a color TFT display and keypad
for local access. The controller provides an Ethernet port and comes with comprehensive webpages for remote access. The
controller has optional SNMP v3 capability for remote system management. The controller supports software upgrade via its USB
port. Refer to the NCU Controller Instructions (UM1M830BNA) for more information.
Vertiv™ NetSure™ -48 VDC Bulk Output Rectifier System Installation and User Manual
Proprietary and Confidential © 2022 Vertiv Group Corp.
1