Page 1
NetSure™ ITS Series +12V DC Power Shelf Installation and User Manual Specification Number: 588706100 Model Number: PSS12/2200-19BC, PSS12/2200-19B...
Page 2
Vertiv™ NetSure™ ITS Series +12V DC Power Shelf Installation & User Manual The information contained in this document is subject to change without notice and may not be suitable for all applications. While every precaution has been taken to ensure the accuracy and completeness of this document, Vertiv assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions.
Vertiv™ NetSure™ ITS Series +12V DC Power Shelf Installation & User Manual TABLE OF CONTENTS Admonishments Used in this Document .......................... v Important Safety Instructions ............................vi Static Warning ..................................viii 1 Customer Documentation Package ..........................1 2 System Description ................................1 3 Installation Acceptance Checklist ..........................
Page 4
Vertiv™ NetSure™ ITS Series +12V DC Power Shelf Installation & User Manual 10.5 Replacement Procedures ..............................................26...
Vertiv™ NetSure™ ITS Series +12V DC Power Shelf Installation & User Manual Admonishments Used in this Document will likely DANGER! Warns of a hazard the reader be exposed to that will result in death or serious injury if not avoided. (ANSI, OSHA)
Vertiv™ NetSure™ ITS Series +12V DC Power Shelf Installation & User Manual Important Safety Instructions Safety Admonishments Definitions Definitions of the safety admonishments used in this document are listed under “Admonishments Used in this Document” on page v. General Safety DANGER! YOU MUST FOLLOW APPROVED SAFETY PROCEDURES.
Page 7
Vertiv™ NetSure™ ITS Series +12V DC Power Shelf Installation & User Manual Personal Protective Equipment (PPE) DANGER! ARC FLASH AND SHOCK HAZARD. Appropriate PPE and tools required when working on this equipment. An appropriate flash protection boundary analysis should be done to determine the “hazard/risk” category, and to select proper PPE.
Vertiv™ NetSure™ ITS Series +12V DC Power Shelf Installation & User Manual Static Warning This equipment contains static sensitive components. The warnings listed below must be observed to prevent damage to these components. Disregarding any of these warnings may result in personal injury or damage to the equipment.
Vertiv™ NetSure™ ITS Series +12V DC Power Shelf Installation & User Manual 1 Customer Documentation Package This document (UM588706100) provides Installation and User Instructions for the NetSure ITS +12 VDC Bulk Output Power System, Spec. No. 588706100. The complete Customer Documentation Package consists of…...
Vertiv™ NetSure™ ITS Series +12V DC Power Shelf Installation & User Manual Rectifier Modules The system ontains rectifier modules, which provide load power. Refer to the Rectifier Instructions (UM1R123000) for more information. 3 Installation Acceptance Checklist Provided below is an Installation Acceptance Checklist. This checklist helps ensure proper installation and initial operation of the system.
Do not attempt to install the system if damage is apparent. If any damage is noted, file a damage claim with the shipping agency within 24 hours and contact Vertiv to inform them of the damage claim and the condition of the equipment.
Page 12
Vertiv™ NetSure™ ITS Series +12V DC Power Shelf Installation & User Manual Figure 4-1: Mounting the Module Mounting Assembly with P/N SXK2310021/1 Mounting Rail Kit P/N SXK2310021/1 Open Compute Rack Mounting Rail Kit (Version 1 Rack) Front P/N 562821 Mounting Rail Kit Procedure Refer to Figure 4-2.
Vertiv™ NetSure™ ITS Series +12V DC Power Shelf Installation & User Manual 4.4 Installing Shipping Support Bracket An Open Compute Rack shipping support bracket is available which allows a module mounting assembly to be integrated into an Open Compute Rack and then shipped to its final destination with rectifier modules installed.
Vertiv™ NetSure™ ITS Series +12V DC Power Shelf Installation & User Manual 5 Making Electrical Connections 5.1 Important Safety Instructions DANGER! Adhere to the “Important Safety Instructions” presented at the front of this document. 5.2 Wiring Considerations All wiring should follow the current edition of the American National Standards Institute (ANSI) approved National Fire Protection Association’s (NFPA) National Electrical Code (NEC), and applicable local codes.
Vertiv™ NetSure™ ITS Series +12V DC Power Shelf Installation & User Manual 5.4 +12 VDC Output Connections Important Safety Instructions DANGER! Adhere to the “Important Safety Instructions” presented at the front of this document. WARNING! Observe proper polarity when making output connections.
Page 16
Vertiv™ NetSure™ ITS Series +12V DC Power Shelf Installation & User Manual Figure 5-2: +12 VDC Output Connections Rear +12V DC Bus (Top, 3 places) (List 01 Shown, other Lists Similar) GND / Return Bus (Bottom, 3 places) Busbar shield removed for clarity only.
Vertiv™ NetSure™ ITS Series +12V DC Power Shelf Installation & User Manual 5.5 External Alarm, Reference, Monitoring, and Control Connections 5.5.1 External Alarm, Reference, Monitoring, and Control Connection Points Locations Refer to Figure 5-3. Figure 5-3: External Alarm, Reference, Monitoring, and Control Connection Points Locations...
Vertiv™ NetSure™ ITS Series +12V DC Power Shelf Installation & User Manual 5.5.6 System Interconnections NOTE! The installation may consist of one (1) main module mounting assembly and up to two (2) expansion module mounting assemblies, or all main module mounting assemblies. In installations with one main module mounting assembly and up to two expansion module mounting assemblies, all module mounting assemblies are on one DC bus and are controlled by a single SCC controller.
Vertiv™ NetSure™ ITS Series +12V DC Power Shelf Installation & User Manual 5.6 AC Input and AC Input Equipment Grounding Connections to Module Mounting Assembly(s) DANGER! Adhere to the “Important Safety Instructions” presented at the front of this document. 5.6.1 Hardwired AC Input Connections NOTE! A grounding conductor must be provided with each AC input feed.
Page 20
Vertiv™ NetSure™ ITS Series +12V DC Power Shelf Installation & User Manual Connections to List 02 Module Mounting Assembly Spec. No. 588706100 List 02 Module Mounting Assembly is configured for two (2) 208 VAC / 240 VAC, 50 Hz / 60 Hz, 3-phase AC input feeds per module mounting assembly.
Page 21
Vertiv™ NetSure™ ITS Series +12V DC Power Shelf Installation & User Manual Connections to List 03 / List 13 Module Mounting Assembly Spec. No. 588706100 List 03 / List 13 Module Mounting Assembly is configured for one (1) 230 VAC / 400 VAC or 240 VAC / 415 VAC, 4-wire + PE, 50 Hz / 60 Hz, 3-phase AC input feed per module mounting assembly.
Page 22
Vertiv™ NetSure™ ITS Series +12V DC Power Shelf Installation & User Manual Connections to List 05 / List 15 Module Mounting Assembly Spec. No. 588706100 List 05 / List 15 Module Mounting Assembly is configured for one (1) 277 VAC / 480 VAC, 4-wire + PE, 50 Hz / 60 Hz, 3-phase AC input feed per module mounting assembly.
Vertiv™ NetSure™ ITS Series +12V DC Power Shelf Installation & User Manual 5.6.2 AC Input Cord Integration AC input cable(s) and plug(s) are factory provided and connected if ordered with a shelf. Refer to “Maximizing Output Power and Optimizing AC Input Current Balancing” in SAG588706100 for output power capacities based on the use of the AC input cable integration and the number and position of rectifiers installed, with and without the convenience outlets providing rated output current (4 amps each).
Page 24
Vertiv™ NetSure™ ITS Series +12V DC Power Shelf Installation & User Manual Figure 5-9: List 430 AC Input Cable Integration (cont’d from previous page) AC Input Connections, 588706100 List 430, AC Line Cord Integration 8 AWG AC Line Cord P/N TFV204001/2, length in feet as ordered.
Page 25
Vertiv™ NetSure™ ITS Series +12V DC Power Shelf Installation & User Manual List 450 AC Input Cable Integration Figure 5-10: List 450 AC Input Cable Integration (cont’d on next page) AC Input Connections, 588706100 List 450, AC Line Cord Integration...
Page 26
Vertiv™ NetSure™ ITS Series +12V DC Power Shelf Installation & User Manual Figure 5-10: List 450 AC Input Cable Integration (cont’d from previous page) AC Input Connections, 588706100 List 450, AC Line Cord Integration For Use With 588706100 List 02...
Page 27
Vertiv™ NetSure™ ITS Series +12V DC Power Shelf Installation & User Manual List 460 AC Input Cable Integration Figure 5-11: List 460 AC Input Cable Integration AC Input Connections, 588706100 List 460, AC Line Cord Integration For Use With 588706100 List 01...
Page 28
Vertiv™ NetSure™ ITS Series +12V DC Power Shelf Installation & User Manual List 532 AC Input Cable Integration Figure 5-12: List 532 AC Input Cable Integration AC Input Connections, 588706100 List 532, AC Line Cord Integration 8 AWG AC Line Cord P/N TFV204001/3, length in feet as ordered.
Page 29
Vertiv™ NetSure™ ITS Series +12V DC Power Shelf Installation & User Manual List 560 AC Input Cable Integration Figure 5-13: List 560 AC Input Cable Integration (cont’d on next page) AC Input Connections, 588706100 List 560, AC Line Cord Integration...
Page 30
Vertiv™ NetSure™ ITS Series +12V DC Power Shelf Installation & User Manual Figure 5-13: List 560 AC Input Cable Integration (cont’d from previous page) AC Input Connections, 588706100 List 560, AC Line Cord Integration AC Input Connections, 588706100 List 560, AC Line Cord Integration...
Vertiv™ NetSure™ ITS Series +12V DC Power Shelf Installation & User Manual 6 Installing SCC Controller and Rectifier Modules NOTE! Install SCC controller and rectifier modules as directed in the “Initially Starting the System” procedure starting on page 24. For SCC controller installation instructions, refer to SCC Controller Instructions (UM1M520HNA).
Vertiv™ NetSure™ ITS Series +12V DC Power Shelf Installation & User Manual 7.3 Initially Starting the System Procedure Apply AC input power to the system by closing ALL external AC disconnects or protective devices that supply AC power to the module mounting assembly.
Vertiv™ NetSure™ ITS Series +12V DC Power Shelf Installation & User Manual 8 Operating Procedures 8.1 SCC Controller and Rectifier Module For operation instructions on these units, refer to the following documents. • SCC Controller Instructions (UM1M520HNA) • Rectifier Module Instructions (UM1R123000) Expected Number of Rectifiers You can set the number of rectifiers expected to be in the system via the controller.
Vertiv™ NetSure™ ITS Series +12V DC Power Shelf Installation & User Manual 10 Troubleshooting and Repair 10.1 Contact Information Refer to Section 4154 (provided with your customer documentation) for support contact information. 10.2 SCC Controller and Rectifier Module For troubleshooting and repair instructions on these units, refer to their separate instruction document.
Page 35
Vertiv™ NetSure™ ITS Series +12V DC Power Shelf Installation & User Manual Connect with Vertiv on Social Media https://www.facebook.com/vertivI https://www.instagram.com/vertiv/ https://www.linkedin.com/company/vertiv/ https://www.twitter.com/vertiv/...
Need help?
Do you have a question about the NetSure ITS Series and is the answer not in the manual?
Questions and answers