Vertiv™ NetSure™ -48 VDC Bulk Output Rectifier System Installation and User Manual
Procedure
NOTE!
The initialization routine takes several minutes. During that time various alarm indicators may illuminate on the NCU
front panel and an audible alarm may sound. Disregard all alarms. An audible alarm can be silenced at any time by
momentarily depressing the ENT key on the NCU Controller.
1.
After the NCU is powered on, the display shows the "Vertiv" screen. The controller is initializing.
2.
When initialization is complete, the language screen appears. Press the up or down arrow key to select the desired language.
Press the ENT key to confirm the selection.
3.
The Main Menu displays. See Figure 9.2.
Figure 9.2 NCU Local Display Main Menu
Main Menu
Date and time are
alternately displayed.
Sys Cap Used: 22.3 %
Press the UP and DOWN keys to highlight
the desired Menu graphic in the Main Menu.
Press the ENT key to enter the selected menu.
To reboot the Controller, from the Main Menu press the ENT and ESC
keys at the same time. Release both keys. Press ENT to confirm.
4.
System information is displayed in multiple screens. Press the ESC key to view other system information. Press the down
arrow key to view the next screen. Press the ESC key to return to the Main Menu.
5.
From the Main Menu, press the UP and DOWN keys to highlight the desired Menu graphic in the Main Menu. Press the ENT
key to enter the selected menu.
NOTE!
Repeatedly press the "ESC" key to return in reverse order level by level from any submenu until the Main Menu
appears.
6.
Refer to the following procedures to verify and set the NCU controller as required for your application.
9.4 Verifying and Setting the NCU Controller as Required for Your
Application
Refer to the NCU Instructions (UM1M830BNA) for additional information.
Refer also to "NCU Start Wizard" on page 19.
18
Green - No Alarm
The number in ( ) indicates
the total number of alarms.
Red - Alarm
Graphics
Proprietary and Confidential © 2022 Vertiv Group Corp.
Menu Name
Description
Alarm
View active alarms and
(Green - No Alarm)
alarm history.
(Red - Alarm)
Gain access to the NCU
Settings
Controller's settings menus.
View AC, Solar, DG, and
Input Power
Wind related information.
View rectifier, solar converter,
Module
and converter module
related information.
View DC equipments
DC
related information.
View battery related
Battery
information.