Summary of Contents for Vertiv NetSure 5100 Series
Page 1
NetSure™ 5100 SERIES -48 VDC Power System User Manual (UM582137100), Revision L Specification Number: 582137100 Model Number: 5100...
Page 2
Vertiv Group Corporation is strictly prohibited. Vertiv and the Vertiv logo are trademarks or registered trademarks of Vertiv Co. All other names and logos referred to are trade names, trademarks or registered trademarks of their respective owners.
Controller, Rectifiers, Solar Converters, and -48 VDC to +24 VDC Converters ................................. 44 Controller Configuration ..........................44 System Troubleshooting Information .................... 44 Replacement Information ........................... 46 Replacement Procedures ........................... 46 Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
Page 4
Replacing a Battery or Load Disconnect Contactor in a List 20, 25 Distribution Cabinet ..............................71 Replacing a Battery or Load Disconnect Contactor in a List 21, 26 Distribution Cabinet ..............................74 Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
(ISO) SAFETY! Informs the reader of general safety information, reminders, precautions, or policies not related to a particular source of hazard or to fire safety. (ISO, ANSI, OSHA) Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
DO NOT apply DC input power to the system until all electrical connections have been completed and checked. Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
• Dispose of used batteries according to the instructions provided with the batteries. Do not dispose of batteries in a fire. They may explode. • ALWAYS FOLLOW THE BATTERY MANUFACTURER’S RECOMMENDATIONS AND SAFETY INSTRUCTIONS. Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
Permits as required by the local authority, per NFPA 70E “Standard for Electrical Safety in the Workplace”. Hazardous Voltage DANGER! HAZARD OF ELECTRICAL SHOCK. More than one disconnect may be required to de-energize the system before servicing. Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
NOTE! When performing any step in procedures that requires removal of existing hardware, retain all hardware for use in subsequent steps, unless otherwise directed. Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
If necessary to repair equipment containing static sensitive components, wear an appropriately grounded wrist strap, work on a conductive surface, use a grounded soldering iron, and use grounded test equipment. Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
• -48 VDC to +24 VDC Converter Instructions: UM1C48241500 • Engineering Drawings • Also provided on the USB drive is a controller configuration drawing and the controller configuration files loaded into the controller as shipped. Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
Temperature probe(s) may also be designated to monitor ambient temperature and/or battery temperature. The controller also provides data acquisition, system alarm management, and advanced battery and energy management. The controller Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
Page 13
Where +24 VDC load power is also required, converter modules are available (depending on configuration, see SAG582137100). These converters operate from the main -48 VDC system bus to provide +24 VDC load power. Refer to the Converter Instructions (UM1C48241500) for more information. Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
OFF, wait 30 seconds or more (until the LEDs on the modules extinguish), then turn input power to the rectifiers and solar converters ON. Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
Optional Transient Voltage Surge Suppressor (TVSS) Device An optional Transient Voltage Surge Suppressor (TVSS) device contains an indicator which illuminates when the circuit activates to suppress voltages. See Figure 3. Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
Page 16
(1-row cabinet shown, 2-row cabinet similar) Optional Critical Alarm Indicator Figure 2: Indicator Locations (List KG) Front FUSE ALARM Figure 3: Optional Transient Voltage Surge Suppressor (TVSS) Device Indicator TVSS Indicator Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
• Current # Break Value (Device Rating.) • Current # High Current Limit (% of Current # Breaker Value.) • Current # Very High Current Limit (% of Current # Breaker Value.) Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
Page 18
A 1Hz flashing indicates a communication failure. Alarm A minor alarm. (Yellow) Alarm A critical or major alarm. (Red) Figure 4: SM-DU Circuit Card in a List 60 Hybrid Connection Cabinet Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
Place the module into an unoccupied mounting position without sliding it in completely. Each module mounting assembly may house rectifier modules, optional solar converter modules, optional -48 VDC to +24 VDC converter modules, and a controller (depending on configuration). Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
Page 20
“Configuring the NCU Identification of Rectifiers”, “Configuring the NCU Identification of Solar Converters”, or “Configuring the NCU Identification of -48 VDC to +24 VDC Converters” in the separate Power System Installation Manual (IM582137100). Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
Page 21
Figure 5: Installing Rectifier and Solar Converter Modules (List 20, 25) Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
Page 22
Figure 6: Installing Rectifier, Solar Converter, and -48 VDC to +24 VDC Converter Modules (List 21, 26) Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
Page 23
The distribution panel is shipped configured Latch with all -48 VDC distribution positions. When using converter modules, you MUST change the last four (4) positions to +24 VDC distribution positions in the field. Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
Page 24
Figure 8: Module Position Identification Label Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
Disconnect the cable coming from the distribution cabinet from the connector on the bottom-most existing module mounting assembly and connect this cable to the same connector on the expansion module mounting assembly. Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
See PD588705300 for additional acceptable module position details. NOTE! When installing in a data cabinet, refer also to “Installing Field Expansion Module Mounting Assembly Spacer Kit, P/N 560075” on page 29. Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
Page 27
Figure 9: Installing a Field Expansion Module Mounting Assembly Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
Page 28
Figure 10: Installing a Field Expansion Module Mounting Assembly - Controller CAN Bus Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
See Figure 12 for an assembly illustration. Must be assembled prior to installation of expansion module mounting assemblies. Assemble spacer kit to outside front surface of data cabinet front vertical rails using M4 flat washer and M4 Keps nut. Torque = 26 in-lbs. Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
Page 30
Figure 12: Installing Field Expansion Module Mounting Assembly Spacer Kit, P/N 560075 Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
Close the distribution cabinet’s front door and turn the latch clockwise or close the system’s enclosure door. Ensure that there are no local or remote alarms active on the system. Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
Page 32
Removing and Retrieving the Lexan Cover from the Front of the Distribution Panel Lexan Lexan Cover Cover Figure 14: Removing the Shorting Busbar and FA Alarm Strap Detail A Alarm Strap Shorting Busbar Detail A Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
Page 33
Moving the Distribution Device Busbar to the Left Remove screws to release the device busbar. Move Busbar and Alarm Spring to the left by one Circuit Breaker position. After Before Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
Page 34
1/4-20 x 5/8 Bolt 1/4” Lock Washer 1/4” Flat Washer Torque to 75 in-lbs. Apply a thin coating of electrical anti-oxidizing compound to the mating surfaces of the busbars. Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
Page 35
Figure 17: Securing the FA Alarm Strap Before After 6-19 x 1/2 Screw Torque to 9.6 in-lbs Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
Page 36
1. Remove polarity label plug buttons. 2. Remove polarity label. 3.Turn over polarity label so other polarity shows. 4. Replace polarity label. 5. Replace polarity label plug buttons. Before After Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
Page 37
Figure 19: Installing the Lexan Cover (Front) 6-19 x 1/2 Screw Torque to 9.6 in-lbs. both sides Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
Page 38
Figure 20: Reworking the Distribution Panel List DA List DB List DC List DD List DE Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
Open the distribution cabinet’s front door by turning the latch in the counterclockwise position or open the system’s enclosure door. Remove the top cover from the distribution cabinet. Figure 21: Removing the Distribution Cabinet Top Cover Remove Top Cover Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
Page 40
Figure 22: Bending Shorting Busbar Shield Top Flap Bend Over Top Flap To Access Shorting Busbar Remove the shorting busbar. Figure 23: Removing the Shorting Busbar Remove Shorting Busbar Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
Page 41
Torque to 23 in-lbs. Relocate Shorting Busbar and Install Cable Torque to 23 in-lbs. Remove the shield from the distribution panel. Figure 25: Removing Distribution Panel Shield Remove this Shield Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
Page 42
Disconnect the wire with the tab from the faston connector. Insulate and tie back Figure 27: Disconnecting Alarm Jumper Disconnect the Alarm Jumper by Separating the Tab from the Faston Connector Here Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
Page 43
Ensure that there are no local or remote alarms active on the system. Close the distribution cabinet’s front door and turn the latch clockwise or close the system’s enclosure door. Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
-48 VDC to +24 VDC converters is not sufficient to maintain this current limit point. If that happens, the current limit point will automatically decrease to the maximum (121% of the remaining rectifiers or 116% of the remaining -48 VDC to +24 VDC converters). Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
Page 45
If the controller resets while a solar converter communications fail alarm is active, the solar converter communications fail alarm is replaced with a solar converter lost alarm. Refer to the NCU Instructions (UM1M830BNA) for a procedure to clear the alarm. Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
Safety fuse covers are provided for all Bussmann GMT type fuses installed in the system. These covers snap onto the fuses and provide protection from exposed electrical terminations when a fuse opens. Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
Page 47
Push the fuse carrier securely back into the mounted fuseholder body. Note that a polarizing key on the bottom of the carrier prevents the carrier from being inserted upside down. Verify no Fuse Alarms are active. Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
Page 48
Push the fuse carrier securely back into the mounted fuseholder body. Note that a polarizing key on the bottom of the carrier prevents the carrier from being inserted upside down. Verify no Fuse Alarms are active. Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
Page 49
Top Lettering on handle must be Insert these terminals right side up. into corresponding sockets on distribution panel. Turn off before installing. Longer Side to the Bottom Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
The following circuit card replacement procedures can be performed with the system operating. Circuit Card Locations Refer to Figure 33, Figure 34, or Figure 35. Figure 32: GMT Distribution Fuse Replacement (List KG) GMT Fuse Safety Cover Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
Page 51
Figure 33: List 20, 25 Circuit Card Locations (1-Row Distribution Cabinet) Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
Page 52
Figure 34: List 21, 26 Circuit Card Locations (2-Row Distribution Cabinet) Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
Page 53
Front (Controller USB-B Port Interface Board) (Factory connected to NCU Controller backplane.) 10M Ethernet Port (RJ-45) Optional IB4 Board LAN Connection USB-A Port (not used) System Interface Board Rear Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
Page 54
After securing the wire, gently tug on the wire to ensure that it cannot be pulled out of the terminal block. Repeat for each wire to be reconnected. Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
Page 55
Remove the grounding wrist strap. Enable the external alarms, or notify appropriate personnel that this procedure is finished. Ensure that there are no local or remote alarms active on the system. Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
Page 56
Jumper J3 on System Interface Board Wire Size Capacity: 16 AWG to 30 AWG. Wire Strip Length: 0.32 inch. Recommended Torque: 2.3 in-lbs. RS485 Connection J3-1: RS485+ J3-2: RS485- Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
Page 57
DANGER! In the next step, external alarm wiring may be energized from an external source. DO NOT allow bare wire ends to contact any grounded or energized object. Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
Page 58
Close the distribution cabinet’s front door. Enable the external alarms, or notify appropriate personnel that this procedure is finished. Ensure that there are no local or remote alarms active on the system. Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
Page 60
(582137100 List 70) Optional EIB Assembly (582137100 List 70) (exploded view) J5-J9 Wire Size Capacity: 16 AWG to 26 AWG. Wire Strip Length: 0.20 inch. Recommended Torque: 2.2 in-lbs. Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
Page 61
Advance Settings Menu / SW Maintenance Tab / Reboot Controller button. Enable the external alarms, or notify appropriate personnel that this procedure is finished. Ensure that there are no local or remote alarms active on the system. Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
Page 62
Figure 39: Replacing an Optional IB4 Board Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
Page 63
Temporarily remove then re-insert the controller. Wait for the controller to initialize. Enable the external alarms, or notify appropriate personnel that this procedure is finished. Ensure that there are no local or remote alarms active on the system. Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
Page 64
Figure 40: Replacing an SM-DU Circuit Card in a List 60 Hybrid Connection Cabinet Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
Figure 41 for hardware build-up and torque. Replace the hardware securing the system load distribution device busbar to the distribution panel. Refer to Figure 41 for hardware build-up and torque. Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
Page 66
Reconnect the AC and DC power sources to the power system. Start the power system. Refer to the separate Installation Instructions (IM582137100) for a startup procedure. Close the distribution cabinet’s front door. Verify no alarms are active. Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
Page 67
Figure 41: Replacing a Distribution Panel in a List 20, 25 Distribution Cabinet Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
Refer to Figure 42 for hardware build-up and torque. Replace the hardware securing the sub-system load distribution device busbar to the distribution panel (if present). Refer to Figure 42 for hardware build-up and torque. Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
Page 69
Reconnect the AC and DC power sources to the power system. Start the power system. Refer to the separate Installation Instructions (IM582137100) for a startup procedure. Close the distribution cabinet’s front door. Verify no alarms are active. Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
Page 70
Figure 42: Replacing a Distribution Panel in a List 21, 26 Distribution Cabinet Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
Reconnect the AC and DC power sources to the power system. Start the power system. Refer to the separate Installation Instructions (IM582137100) for a startup procedure. Verify no alarms are active. Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
Page 72
Figure 43: Replacing a Battery or Load Disconnect Contactor in a List 20, 25 Distribution Cabinet Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
Page 73
Figure 44: Battery or Load Disconnect Contactor Wiring Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
Reconnect the AC and DC power sources to the power system. Start the power system. Refer to the separate Installation Instructions (IM582137100) for a startup procedure. Verify no alarms are active. Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
Page 75
Figure 45: Replacing a Battery or Load Disconnect Contactor in a List 21, 26 Distribution Cabinet Vertiv | NetSure 5100 Series User Manual (UM582137100) | Rev. L...
Need help?
Do you have a question about the NetSure 5100 Series and is the answer not in the manual?
Questions and answers