Procedure
1.
For 23" mounting, attached the 23" mounting bracket adapter plates to the standard 19" mounting brackets.
2.
Position the system in the relay rack or cabinet equipment rack.
3.
Secure the system to the relay rack or cabinet equipment rack using hardware as shown in Figure 6.1 (see Figure 6.1 for
recommended torque). Use grounding washers as indicated in Figure 6.1.
NOTE!
Install (orient) the ground washers so the teeth dig into the mounting angles for a secure ground connection.
NOTE!
Compliance with Telcordia GR-1089-CORE requires that prior to mounting the system to the equipment rack:
All paint must be removed from the front surface of each equipment rack rail where it mates with a shelf-mounting
bracket, so that good metal-to-metal contact can be established between the shelf and rack.
The shelf-to-rack mating surfaces must be cleaned.
Electrical anti-oxidizing compound must be applied to the shelf-to-rack mating surfaces.
Figure 6.1 Mounting the System in a Relay Rack or a Cabinet Equipment Rack

7 Making Electrical Connections

7.1 Important Safety Instructions

DANGER! Adhere to the "Important Safety Instructions" presented at the front of this document.

7.1.1 Wiring Considerations

All wiring, branch circuit protection, and grounding should follow the current edition of the American National Standards Institute
(ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code (NEC), and applicable local codes. For
operation in countries where the NEC is not recognized, follow applicable codes.
Refer to drawing 031110100 for lug crimping information. Refer to drawings 031110200 and 031110300 for additional lug information.

7.2 Relay Rack / Cabinet Frame Grounding Connection

For relay rack / cabinet frame grounding requirements, refer to the current edition of the American National Standards Institute
(ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code (NEC), applicable local codes, and your
specific site requirements.
Vertiv™ NetSure™ -48 VDC Bulk Output Rectifier System Installation and User Manual
Front
Proprietary and Confidential © 2022 Vertiv Group Corp.
MOUNTING HARDWARE
12-24 x 3/4" Thread Forming
Hex Head Screw
No. 10/12 Ground Washer
Torque: 65 in-lbs.
11