This product is intended for installation in network telecommunication facilities (CO, vault, hut, or other environmentally
controlled electronic equipment enclosure).
This product is intended to be connected to the common bonding network in a network telecommunication facility (CO,
vault, hut, or other environmentally controlled electronic equipment enclosure).
The DC return connection to this system can remain isolated from system frame and chassis (DC-I).
This system is suitable for installation as part of the Common Bonding Network (CBN).
System ventilating openings must not be blocked and temperature of air entering rectifiers must not exceed the rated
operating ambient temperature range.
Clearance requirements are (relay rack):
-
Recommended minimum aisle space clearance for the front of each bay is 2' 6".
-
Recommended minimum aisle space clearance for the rear of each bay is 2' 0".
Clearance requirements are (cabinet mounting):
-
Recommended minimum clearance for the rear of the system is 4".

3.3 Compliance Information

Safety Compliance: This unit meets the requirements of UL 60950-1, Standard for Information Technology Equipment, and is UL
Recognized as a power supply for use in Telephone, Electronic Data Processing or Information Processing Equipment. This unit
meets the requirements of CAN/CSA 22.2, No. 60950-00 and is tested and Certified by UL ("c UR") as a Component Type Power
Supply.
NEBS Compliance: Compliance verified by a Nationally Recognized Testing Laboratory (NRTL) per GR-1089-CORE and GR-63-
CORE. Contact Vertiv for NEBS compliance reports.
Rectifier Modules: In order to remain compliant during a fan failure condition, the backup battery connection must be utilized to
provide sufficient power to the loads for up to eight (8) hours when the system is operated at greater than 50% output power. If no
backup battery connection is used, the system must operate with a redundant module installed.

3.4 Rectifier

Refer to the Rectifier Instructions (UM1R482000e3).

3.5 Controller

Refer to the NCU Controller Instructions (UM1M830BNA).
For controller factory settings, refer to the Controller Configuration Drawing (C-drawing).

3.6 Dimensions and Weight

See Figure 3.1.
Vertiv™ NetSure™ -48 VDC Bulk Output Rectifier System Installation and User Manual