Vertiv NetSure-48 VDC Installation And User Manual page 20

Bulk output rectifier system
Hide thumbs Also See for NetSure-48 VDC:
Table of Contents

Advertisement

Vertiv™ NetSure™ -48 VDC Bulk Output Rectifier System Installation and User Manual
Procedure
1.
AC input connections are made using the AC input cable assemblies or line cords ordered with the system. These are
connected to the plug-in Molex connectors located on the rear of the shelf. Connect the other end of the AC input cable
assemblies or line cords to a properly wired AC outlet or distribution box. Refer to Figure 7.3.
Table 7.2 Recommended Rectifier AC Input Branch Circuit Protection (Nominal 120 VAC / 208 VAC / 240 VAC, Single Phase,
50 Hz / 60 Hz) Supplied Input Cable Assemblies
(see "Rectifier AC Input Cable Assemblies and Rectifier AC Input Line Cords" on page 5)
Input Voltage
120 VAC
208 VAC
240 VAC
1
The AC input branch circuit protective device should be of the time-delay or high inrush type.
2
Input current based on R48-2000e3 rectifier module.
Table 7.3 Recommended Rectifier AC Input Branch Circuit Protection (Nominal 120 VAC / 208 VAC / 240 VAC, Single Phase,
50 Hz / 60 Hz) Supplied AC Input Line Cords
(see "Rectifier AC Input Cable Assemblies and Rectifier AC Input Line Cords" on page 5)
Input Voltage
120 VAC
208 VAC
240 VAC
The AC input branch circuit protective device should be of the time-delay or high inrush type.
1
Input current based on R48-2000e3 rectifier module.
2
14
Recommended Rectifier AC Input Branch Circuit Protection
(Nominal 120 VAC / 208 VAC / 240 VAC, Single Phase, 50 Hz / 60 Hz)
Supplied Input Cable Assemblies
(One AC Input Branch Circuit per Two Rectifier Modules)
Input Current (2)
18 A
20 A
17.5 A
Recommended Rectifier AC Input Branch Circuit Protection
(Nominal 120 VAC / 208 VAC / 240 VAC, Single Phase, 50 Hz / 60 Hz)
Supplied AC Input Line Cords
(One AC Input Branch Circuit per Two Rectifier Modules)
Input Current (2)
18 A
20 A
17.5 A
Proprietary and Confidential © 2022 Vertiv Group Corp.
Overcurrent Protection (1)
30 A
25 A
25 A
Overcurrent Protection (1)
Size per AC Line
Cord Plug Rating