Vertiv™ NetSure™ -48 VDC Power System Quick Start Guide
5 Electrical Connections
5.1 Important Safety Instructions
DANGER! Adhere to the "Important Safety Instructions" presented at the front of this document.
5.2 Relay Rack / Cabinet Frame Grounding Connection
For relay rack / cabinet grounding requirements, refer to the current edition of the American National Standards Institute (ANSI)
approved National Fire Protection Association's (NFPA) National Electrical Code (NEC), applicable local codes, and your specific site
requirements.
5.3 Central Office Ground Connection
Landing points are provided on the battery return bus for a central office ground lead (see Figure 25 or Figure 26). For central office
grounding requirements, refer to the current edition of the American National Standards Institute (ANSI) approved National Fire
Protection Association's (NFPA) National Electrical Code (NEC), applicable local codes, and your specific site requirements.
5.4 Ground Connection to a Transient Voltage Surge Suppressor (TVSS)
Devices
Refer to the procedure in "Install and Wire Transient Voltage Surge Suppressor (TVSS) Devices" on page 5.
5.5 AC Input and AC Input Equipment Grounding Connections to 588705300
Module Mounting Shelf(s)
Refer to AC Input and AC Input Equipment Grounding Connections to 588705300 Module Mounting Shelf(s) in MAKING
ELECTRICAL CONNECTIONS section of the Installation Instructions (IM582137000) for a complete procedure.
DANGER! Adhere to the "Important Safety Instructions" presented at the front of this document.
There are several options to provide AC inputs to the 588705300 module mounting shelf. See PD588705300.
1.
For factory installed module mounting shelves without plug-in AC input connectors, AC input leads are factory connected
from the module mounting shelf AC input terminals to an AC input termination assembly provided in the system/cabinet.
Refer to the system/cabinet documentation for connection details to the AC input termination assembly. Refer to the
system/cabinet documentation for recommended AC input branch circuit protection.
2.
For a field installed module mounting shelf in a system with a List 27 distribution cabinet or if a List 7 distribution cabinet
system is used in a relay rack and not a system cabinet, the module mounting shelf is equipped with plug-in AC input
connectors located on the rear of the shelf. AC input cable assemblies with mating connectors are available (see Power Data
Sheet PD588705300). Refer to Power Data Sheet PD588705300 for recommended AC input branch circuit protection. See
PD588705300 and Figure 6.
6