Vertiv™ NetSure™ -48 VDC Bulk Output Rectifier System Installation and User Manual
4.
To Change a Parameter:
Press the UP and DOWN keys to move up and down the list of parameters. Press ENT to select the parameter. Press the UP
and DOWN keys to change the parameter. Press ENT to make the change. Press ESC to cancel the change.
5.
Table 9.1 shows the menu navigation for some basic settings. Refer to the separate NCU Manual (UM1M830BNA) supplied
with your power system for complete Local Display menus.
Table 9.1 NCU Basic Settings Menu Navigation
Parameter
Date
Time
IP Communications Parameters
(IP address, subnet mask address, gateway
address)
Float Voltage
Equalize Voltage
Battery Current Limit
Battery Capacity
Reset Battery Capacity
HVSD Limit
Rectifier Current Limit
Over Voltage Alarm 1
Over Voltage Alarm 2
Under Voltage Alarm 1
Under Voltage Alarm 2
Changing Battery Capacity Rating in the NCU
NOTE!
After setting the battery capacity, the User should also reset the battery capacity (battery must be fully charged).
1.
Change the battery capacity setting of the NCU to match the battery connected to the power system.
Local Menu Navigation:
Main Menu / Settings Icon / Batt Settings / Batt1 Settings or Batt2 Settings / Rated Capacity.
Web Menu Navigation:
Settings Menu / Battery Tab / Batt1 Rated Capacity and Batt2 Rated Capacity.
2.
Reset the battery capacity (resets the battery capacity calculation).
NOTE!
Only reset the battery capacity when the battery is fully charged; otherwise, the battery charge status may not be
accurate.
Local Menu Navigation:
Main Menu / Settings Icon / Batt Settings / Basic Settings / Reset Batt Cap.
Web Menu Navigation:
Settings Menu / Battery Tab / Reset Battery Capacity.
Refer to the NCU Instructions (UM1M830BNA) for detailed instructions.
20
Main Menu / Settings Icon / Sys Settings / Date.
Main Menu / Settings Icon / Sys Settings / Time.
Main Menu / Settings Icon / Comm Settings / enter parameters.
Main Menu / Settings Icon / Batt Settings / Charge / Float Voltage.
Main Menu / Settings Icon / Batt Settings / Charge / EQ Voltage.
Main Menu / Settings Icon / Batt Settings / Curr Limit Mode and Batt Curr Limit.
Main Menu / Settings Icon / Batt Settings / Batt1 Settings or Batt2 Settings / Rated Capacity.
Main Menu / Settings Icon / Batt Settings / Basic Settings / Reset Batt Cap
Web Menu Navigation Only: Settings Menu / Rectifiers Tab / HVSD (set to enabled) then set HVSD Limit.
Main Menu / Settings Icon / Rect Settings / Current Limit (set to enabled) then set Curr Limit Pt.
Main Menu / Settings Icon / Other Settings / Over Voltage 1.
Main Menu / Settings Icon / Other Settings / Over Voltage 2.
Main Menu / Settings Icon / Other Settings / Under Voltage 1.
Main Menu / Settings Icon / Other Settings / Under Voltage 2.