Nominal 208 Vac, 240 Vac, 277 Vac, Or 277 Vac / 480 Vac Input And Equipment Grounding Connections (If Equipped) - Vertiv NetSure 7100 Series Installation Manual

-48v dc power system
Hide thumbs Also See for NetSure 7100 Series:
Table of Contents

Advertisement

Nominal 208 VAC, 240 VAC, 277 VAC, or 277 VAC / 480 VAC Input and Equipment
Grounding Connections (if equipped)
System components are factory mounted in a relay rack, on shipping rails, or in an enclosure as specified when
ordered.
DANGER! Adhere to the "Important Safety Instructions" presented at the front of this document.
General
NOTE THAT THIS SYSTEM MAY BE EQUIPPED WITH AC OR DC INPUTS. THESE PROCEDURES
APPLY TO SYSTEMS WITH AC INPUTS. SPECIFICALLY, THESE PROCEDURES APPLY TO THE
FOLLOWING EQUIPMENT:
• 582127000 List 40, 41, 42, 43
• 588705000 List 21, 22, 31, 32, 33
• 588705300 List 01, 03, 21
• 588705400 List 01, 02, 03, 04
• 588705500 List 01, 02, 03, 04, 05
Wiring Considerations
For wire size, branch circuit protection, crimp lug, and general wiring recommendations; refer to System
Application Guide SAG582127000.
AC Input Termination Assemblies
The available AC input options for this system are:
• The system can be equipped with an AC input termination assembly which provides a separate single
phase AC input connection for each rectifier position (582127000 List 40).
• The system can be equipped with an AC input termination assembly which provides a separate single
phase AC input connection for every two (2) rectifier positions (582127000 List 41).
• The system can be equipped with an AC input termination assembly which provides a separate three
phase AC input connection for every three (3) rectifier positions (582127000 List 42 and List 43).
Vertiv