5.6 AC Input and AC Input Equipment Grounding Connections to Module
Mounting Assembly(s)
DANGER! Adhere to the "Important Safety Instructions" presented at the front of this document.

5.6.1 Hardwired AC Input Connections

NOTE!
A grounding conductor must be provided with each AC input feed.
AC input cable(s) and plug(s) are factory provided and connected if ordered with a shelf. See "AC Input Cord Integration" starting on
page 15.
Connections to List 01 Module Mounting Assembly
Spec. No. 588706100 List 01 Module Mounting Assembly is configured for one (1) 208 VAC / 240 VAC, 50 Hz / 60 Hz, 3-phase AC
input feed per module mounting assembly. Feeds 208 VAC / 240 VAC input voltage to each module (9 modules per shelf) plus the
convenience AC outlets.
If a cable was not ordered with the shelf, customer to install conduit or cord grips using the AC input access hole in the rear of the
shelf, and wire to the AC input terminal block located behind the rear access cover. See Figure 5-5. See System Application Guide
(SAG588706100) for recommended wire size and branch circuit protection device rating.
Figure 5-5: AC Input Connections to a 588706100 List 01 Module Mounting Assembly (Hardwired)
AC Input Connections, 588706100 List 01, Hardwired
Nominal 208 VAC / 240 VAC, 50 Hz / 60 Hz, 3-Phase, 1 Feed per Module Mounting Assembly
(1 Feed per 9 Module Positions)
Rear (back panel removed for clarity only)
Rectifier Module
Mounting Positions
#1
#2
#3
#4
Front
Convenience
Outlet #1
(Positions #1 - #9)
208 VAC / 240 VAC,
50 Hz / 60 Hz, Three Phase
L1 - L2: Position #1, #4, #7
L2 - L3: Position #2, #5, #8
L1 - L3: Position #3, #6, #9
L1 - L3: Convenience Outlet #1
L1 - L2: Convenience Outlet #2
Vertiv™ NetSure™ ITS Series +12V DC Power Shelf Installation & User Manual
#5
#6
#7
#8
#9
GND
FRAME GROUND CONNECTION
L1
L2
L3
One M6 stud and hardware.
Torque: 5.7 Nm (50 in-lbs.)
AC Feed
AC INPUT
Wire Size Capacity: 16 to 2 AWG.
Torque: 2.5 to 4.5 Nm (22.1 to 39.8 in-lbs.)
Convenience
Outlet #2
11