Plc Configuration; Units; Program Generator - JUMO variTRON 300 Operating Manual

Automation system central processing unit
Hide thumbs Also See for variTRON 300:
Table of Contents

Advertisement

5.8

PLC configuration

5.8.1

Units

These settings are relevant for the automatic conversion performed when the temperature unit is
changed (°C/°F) (relates only to the PLC application).
Parameter
Setting for abso-
lute temperature
Setting for rela-
tive temperature
5.8.2

Program generator

Nine independent program generators are available as an optional extra (extra code 225 required),
meaning that nine independent programs can run asynchronously at the same time.
The following description applies for program generators 1 to 9.
General
Parameter
Name of program
generator
Function
Program start
Response by out
of range (O-o-R)
(behavior at O-o-
R)
Selection/data input
°C
°F
K
°C
°F
K
Selection/data input
Enter text (or use existing text) Designation of program generator
Inactive
Program generator
Fixed-setpoint generator
Program start
Actual value
Time
Continuation
Program stop
5 Configuration
Description
Unit for temperature value
Deg. Celsius
Deg. Fahrenheit
Kelvin
Unit for temperature difference
Deg. Celsius
Deg. Fahrenheit
Kelvin
Description
The program generator is switched off.
The program generator is controlled by a program.
The program generator operates as a fixed-set-
point generator. In this case, the setpoint values for
the basic status or manual mode are used.
The program starts at the first programmed set-
point value.
The program starts at the point at which the set-
point value corresponds to the current actual val-
ue.
A start time specified for program start is adopted
as the start time in a 24 h program.
Example:
Start time: 06:00:00; 24 h program from 00:00 to
24:00: The program starts at 6 a.m. and runs until
midnight.
Behavior of the program generator if measuring
range is exceeded or if there is measuring range
underflow (Out-of-Range)
Program continues to run.
The program is stopped.