Transfer settings
Parameters/functions:
System state after configuration transfer (as of system version 5):
Unchanged: After the transfer, the device returns to the system state it had before the transfer.
STOP: The device remains in the "Stop" system state after transmission.
Complete configuration: All data packets are transferred.
Selective configuration: Only the selected data packets (or parts thereof) are transferred.
In order to send a data packet (send it to the device) or export it (to a file), select the data packet
concerned using the button (= red).
In order to extract a data packet (load it from the device) or import it (from a file), select the relevant
option from the drop-down menu:
Do not transfer: The data packet concerned is not transferred.
Only visible values of known parameters: Only the values of existing parameters are applied in
the setup project. The structure is not modified.
Structure and values (only for "Bus" and "PLC Parameter"): In the case of the PLC parameters,
by selecting this option you can apply a PLC parameter structure that is already in the device in
the setup project.
Caution! The PLC parameter structure that is already in the project will therefore be lost.
Only values of known parameters (only for "PLC Parameter"): The structure of the PLC param-
eters is not modified in the setup project. However, known parameters in the project structure are
applied from the device structure.
Only modify structure (only for "PLC Parameter"): The structure in the setup project is adjusted
to the structure of the device. However, existing parameters are not modified.
Complete configuration including device-specific data (as of system version 3): In addition, device-
specific data is transmitted, for example device ID, IP address, password, activation of options.
Selective configuration including device-specific data (as of system version 3): In addition, device-
specific data is transmitted (see above).
NOTE!
The default settings are suitable for most application scenarios and should only be modified by experi-
enced users.
CAUTION!
While the configuration is being sent to the device, it goes into the "Stop" system state.
This interrupts the processing of the PLC application.
 The user must ensure that this does not have any negative effects on the ongoing operation of the
plant.
Default settings:
Transfer type for sending or export: Complete configuration (as of system version 3: selective conf.)
Transfer type for extraction or import: Selective configuration
Data packet
User management (Ac-
cessControlManager)
Device manager
System bus
Data carrier manage-
ment
(as of system version 7)
Send/Export
No (= gray)
Yes (= red)
Yes (= red)
No (= gray)
Extract/import
Do not transfer
Only visible values of known parameters
Structure and values
Do not transfer
4 Operation