Advertisement

5.12

Real-time processing

5.12.1

Data recording

The process values (analog and digital signals) to be recorded are selected here (available as of system
version 6). The process values are organized in groups as analog or digital channels. The input signals
of the channels are selected from a selector.
Grouping of signals (channels) allows the user, for example, to create a separate group for each plant
or to record signals with different memory cycle.
The maximum number of channels (analog and digital) that can be recorded depends on the device
(variTRON 300: 60 channels; variTRON 500: 240 channels). However, the number of licensed channels
is decisive for the evaluation of the recorded data (fee-based licenses for JUMO smartWARE Evalua-
tion).
NOTE!
The user must ensure that the maximum number channels is not exceeded (60 or 240). The sum of an-
alog and digital channels of all groups is decisive for this.
If the maximum number of channels is exceeded during the configuration of a group, this results in the
complete group not being recorded. In case of configuration with the Web Cockpit, a fault message is
immediately entered into the event list.
NOTE!
The process values are only temporarily stored in the central processing unit to bridge network failures
before these values are transferred to the Datastore for storage. The Datastore is part of the JUMO
smartWARE Evaluation software. A visualization using only the central processing unit is not possible.
Parameter
Parameter
Name
Analog channels
Parameter
Input signal
As of system version 6:
Designation
Replace designa-
tion
Start of display
range
Selection/data input
Enter text (or use existing text) Designation of the group
Selection/data input
Select signal from selector
Enter text (or use existing text) Designation of the signal
Inactive
Active
-99999 to 99999 (0)
As of system version 7:
-1.7e+307 to 1.7e+307
5 Configuration
Description
The designation is displayed in the visualization
(JUMO smartWARE Evaluation).
Description
Analog signal
System version 5: Analog PLC outputs (analog
values 001 to 120)
As of system version 6: Additional analog signals
available (values of the system monitoring, pro-
cess values of the modules).
If active:
Data evaluation: The original designation is re-
placed by the designation used here.
Lower limit of display range
85