Parameter
Post-trigger time
[s]
Memory rate
[hh:mm:ss]
Time operation
This function is available as of system version 7.
Time operation has higher priority compared with standard operation, but lower priority than event oper-
ation.
Parameter
Start
[hh:mm:ss]
End
[hh:mm:ss]
Memory rate
[hh:mm:ss]
Recorded values
The following values are determined within a recording interval:
Current value (current value at the end of the interval)
Measured value status (status of the current value according to NAMUR NE107)
Minimum value (for digital signal: number of low values (logical 0))
Maximum value (for digital signal: number of high values (logical 1))
Average value (for digital signal: number of high values in relation to the number of low values)
Number of values with measuring range underflow
Number of values with measuring range overflow
Number of valid value
Number of invalid values
Selection/data input
0 to 10 (0)
00:00:01 to 24:00:00
(00:00:01)
Selection/data input
00:00:00 to 23:59:59
(00:00:00)
00:00:00 to 23:59:59
(00:00:00)
00:00:01 to 24:00:00
(00:00:01)
5 Configuration
Description
Extends event operation after the control signal
has been deactivated.
Recording interval
Time interval at which the values of the analog and
digital signals of the group are stored for evalua-
tion.
Description
Time at which the time operation is started.
Start = End: Time operation is not active.
Time at which the time operation ends.
Recording interval
Time interval at which the values of the analog and
digital signals of the group are stored for evalua-
tion.