Customer-Specific Linearization - JUMO variTRON 300 Operating Manual

Automation system central processing unit
Hide thumbs Also See for variTRON 300:
Table of Contents

Advertisement

Parameter
Server 1
Server 2
Server 3
Maximum round-
trip time
Date and time
Parameter
Time
5.2.1

Customer-specific linearization

You can use the customer-specific linearization to create a customized linearization characteristic line
for analog values. Two procedures are available for this: formulas or grid values (value pairs).
Temperature values must always be specified in °C. In general, use the measuring units without prefixes
(e.g. A instead of mA).
Formula
Customer-specific linearization is specified using a polynomial. The polynomial is calculated for the en-
tire linearization range.
Example (4th order polynomial): y = X4*x
Parameter
Name
Measuring range
start (Ymin)
Measuring range
end (Ymax)
Decimal places
Polynomial:
X0
X1
X2
X3
X4
Selection/data input
Enter the address of the time
server (or use an existing ad-
dress)
Example: de.pool.ntp.org
0 bis 99999
(5)
Selection/data input
Enter the date and time
4
Selection/data input
Enter text (or use existing text) Designation of linearization
-99999 to 99999
(0)
-99999 to 99999
(100)
0 to 6
(4)
-99999 to 99999
(0)
-99999 to 99999
(1)
-99999 to 99999
(0)
-99999 to 99999
(0)
-99999 to 99999
(0)
Description
Up to three time servers can be entered.
The server list is processed top down, in other
words, the next time server on the list is only que-
ried if the previous server is unreachable.
It must be ensured that the server name is re-
solved to an IP address via a DNS server (see
Configuration > Ethernet).
Maximum time in seconds between the client's re-
quest and the server's response (for local time
server).
Description
Device's time settings (NTP must be inactive)
In the web application, the PC's time settings are
applied (the current time in the device is not
shown). These settings can be changed individual-
ly.
3
2
+ X3*x
+ X2*x
+ X1*x + X0
Description
Start value of the y axis
End value of the y axis
Number of decimal places
Absolute component of the polynomial (point of in-
tersection with the y axis)
Coefficient of the linear component (x)
Coefficient of the quadratic
component (x
Coefficient of the cubic component (x
Coefficient of the quartic component (x
5 Configuration
2
)
3
)
4
)
71

Advertisement

Table of Contents
loading

This manual is also suitable for:

705003

Table of Contents