Wtrans Gateway - JUMO variTRON 300 Operating Manual

Automation system central processing unit
Hide thumbs Also See for variTRON 300:
Table of Contents

Advertisement

5 Configuration
5.15

Wtrans gateway

Settings for using the JUMO Wtrans transmitters are made here (available as of system version 5).
General
Parameter
Radio frequency
Wtrans transmitter
These settings are required for each transmitter selected in the Wtrans hardware configuration (Wtrans
hardware assistant in the Setup program).
Parameter
General
Name
Transmitter ID
Radio timeout
Analog processing
Name
(for Wtrans E01;
as of system ver-
sion 6)
Factor
Offset
Linearization
NOTE!
Wtrans B (707060) with thermocouple: With system version 5, only types J, K, and B are supported. With
system version 6, all types except MoRe5-MoRe41 and W3Re-W26Re are supported.
90
Selection/data input
868.4
912.6 to 917.4
Selection/data input
Enter text (or use existing text) Transmitter designation
0 to 99999
2 to 20
Enter text (or use existing text) Designation of measured value
-99999 to 99999
(1)
-99999 to 99999
(0)
Select linearization from selec-
tor (customer-specific linear-
ization: formula or grid points)
Description
Wtrans radio frequency (MHz)
Europe
America, Australia, Canada and New Zealand
Description
ID of the Wtrans transmitter
The unique ID set on the transmitter side must also
be set here to identify the transmitter.
Number of radio telegrams not received, which
leads to timeout detection.
The set transmission interval of the transmitter is
transmitted with the radio telegram. When the first
telegram is received, this value is saved in the re-
ceiver and the radio timeout monitoring function is
activated. If no new telegram is received through-
out the entire timeout period, the measured value
is set to "no input value" and the "Radio timeout"
alarm is activated.
Factor for correction of the measured value
Offset value for correction of the measured value
Linearization for the measured value
Configuration of linearization: Configuration > De-
vice manager > Customer-specific linearization

Advertisement