5 Configuration
5.10

Programs

Each program (each program plan) can consist of a maximum of 200 program sections. Up to 30 setpoint
values and up to 32 operating contacts can be used in each program section.
Tolerance band monitoring can be set up for the first setpoint value. This means that the relevant actual
value is monitored; if it leaves the tolerance band, the program is stopped until it returns to a value that
is within the tolerance band (depending on configuration).
A total of up to 300 programs can be managed in a program pool.
A program generator is required to execute a program. A program can also be assigned multiple pro-
gram generators.
The following description applies to program plans 001 to 300.
Program header
Parameter
Program GUID
Program name
Program informa-
tion
Pictogram name
Favorite
Repetitions
Program assign-
ment (allocation)
Number of repeti-
tions
Assignment (allo-
cation)
82
Selection/data input
Enter ID
(0)
Enter text (or use existing text) Designation of the program
Enter text (or use existing text) Description of the program
Select pictogram
No
Yes
Inactive
Endless
Number
-9223372036854775808 to
9223372036854775807
(0)
0 to 99999
Off (FALSE)
On (TRUE)
Description
ID for uniquely identifying the program (length: 64
bits)
Pictogram (icon) for graphical identification mark-
ing of the program
Programs marked as favorites are placed at the
start of the program start menu. If there is more
than one favorite, the program number is the deci-
sive criterion (in ascending order).
Program is not a favorite
Program is a favorite
Cyclic program repetition
The program is not repeated (only one program
run).
The program is repeated endlessly.
The program is repeated as many times as is
specified by the parameter "Number of repeti-
tions".
Number (length: 64 bits) for assigning a program to
a plant or a group.
This number can be used in the customer-specific
application to group similar programs.
Number of program repetitions
Selection of program generators to be used to ex-
ecute the program.
Program generator not selected
Program generator selected