JUMO variTRON 300 Operating Manual page 78

Automation system central processing unit
Hide thumbs Also See for variTRON 300:
Table of Contents

Advertisement

5 Configuration
Parameter
Power off
Start with time
Actual-value dif-
ference
End signal (s)
Events
(Program start,
...)
Event text
Names of operating contacts
Parameter
Name of contact
01 to
Name of contact
32
78
Selection/data input
Abort
Continuation
Standstill
Continuation at x %
Continuation at actual value
No
Yes
0 to 100
0 to 32767
Off (FALSE)
On (TRUE)
Enter text (or use existing text) This text is entered into the event list in case of the
Selection/data input
Enter text (or use existing text) Designation of the operating contact concerned
Description
Behavior of the program generator when the pow-
er failure is over.
The program is aborted; the program generator
enters basic status.
The program continues running from the point that
it was at when the power failed.
The program is stopped (program generator stays
in automatic mode).
The program can be continued or aborted by
means of operation.
If the difference in the actual value (before and af-
ter the power failure) is less than or equal to x %,
the program continues running from the point that
it was at when the power failed. If this is not the
case, the program generator enters standstill.
The program continues running at the actual value;
consideration is given to whether the program pro-
file had a positive or negative slope at the time of
the power failure.
The program can be started at a specific time (en-
try of date and time by means of operation).
Immediate program start (e.g., by means of opera-
tion or digital signal)
Program start at a specific time
The maximum admissible difference between the
actual value before and after the power failure for
the program to continue running.
Length of the program end signal
Activate the event message for the relevant event.
No event message
The event is entered in the event list.
event.