4 Operation
Logoff
1) Press the "Menu/OK" key to open the device menu.
2) Switch to the submenu "User administration > Logoff".
3) Press the "Menu/OK" key.
4.2.4

Reset to factory settings

To perform a reset to default settings, first switch off the device (device disconnected from the voltage
supply), then simultaneously press the "Menu/OK" (6) and "Down" (7) keys, and then switch the device
back on (restore the voltage supply). When doing so, press and hold the keys until the display's backlight
has been activated.
CAUTION!
Reset to default settings
All data will be deleted. All settings will be reset to the default settings (JUMO), including the user admin-
istration settings (user "Master", password "9200").
 Back up the hardware configuration and settings beforehand using the setup program.
NOTE!
Resetting to factory settings with the "Menu/OK" (6) and "Down" (7) keys also removes the extra codes
(chargeable functions). For this reason, the files for enabling the extra codes (also referred to as license
files or FeatureResponse files) should be stored after initial receipt in such a way that they are available
again for transfer to the device after a factory reset (see JUMO Web Cockpit > Service).