39 Connection distributor Battery

The battery power supply of the DualGuard-S 28 or
DualGuard-S 20 is provided by a modular battery connec-
tion distributor. The distributor contains a size 00C switch-
disconnector with a maximum connection cross-section of
50 mm2 and enables the connection of up to 6 substations
to modular size D02-E18 battery outgoing distributors and
the associated terminals for the earth conductors. The com-
ponents are simply plugged on from the front and securely
contacted.
Name:
Assembly:
Degree of protection:
Protection class:
Rated voltage (Battery):
Rated current (Battery):
Maximum number of outgoing distributors
modules
Module
Terminals Connection cross-sections
Mains feed:
Terminals Connection cross-sections
Mains Distribuiton:
Ordering details
Type
Outgoing distribution module Battery
for busbar mounting
Busbar cover profile
Mounting- and Operating Instruction CEAG DualGuard-S 40071860347 January 2020 www.ceag.de
Data:
On busbar
IP20
I
216 V DC
IN =63 A
6
50 mm² Rigid/flexible
16 mm² Rigid/flexible
50 mm² Rigid/flexible
Description
Incl. 2 pieces screw caps E18 and 3 pieces D02-
fuse links 25A
Cover profile in module width for clip mounting to
the bottom tray profile
39 Connection distributor Battery
Pos.
Order No.
40071347161
40071347192