Circuit Breaker Tests Before Energizing The Switchgear - Eaton Ulusoy HMH24-04 User Manual

Incoming/outgoing switchgear with circuit breaker
Table of Contents

Advertisement

Circuit Breaker Tests Before Energizing the Switchgear

Starting conditions:
Switchgear front door is closed, disconnector is open,
Earthing switch is closed, circuit breaker is open and locked.
OPERATIONAL
DIAGRAM
CLOSE
THE SWITCHGEAR
DOOR
ULUSOY ELEKTRİK A.Ş.
OPEN
1.ORGANİZE SANAYİ BÖLGESİ OĞUZ CAD. NO: 6
THE EARTHING
06935 SİNCAN / ANKARA TÜRKİYE
SWITCH
0
TEL: +90 312 267 07 12
FAX: +90 312 267 05 17
www.eaton.com /
www
CHARGE
ulusoy.info@eaton.com
THE SPRING
(DISCONNECTOR)
Standard: IEC 62271-200
Protect on Degree: IP3X
CLOSE
THE SWITCH
DISCONNECTOR
CHARGE
THE SPRING
(CB)
CLOSE
I
THE CIRCUIT
BREAKER
OPEN
0
THE CIRCUIT
BREAKER
NO
IS THERE ANY
OPERATION ON
THE SWITCHGEAR?
YES
OPEN
THE SWITCH
0
DISCONNECTOR
0
CLOSE
THE EARTHING
SWITCH
I
OPEN
THE SWITCHGEAR
DOOR
!
IF THIS SWITCHGEAR IS USED AS AN
INCOMING FEEDER DO NOT CLOSE
THE EARTING SWITCH BEFORE CUTTING
DOWN THE ENERGY FROM PREVIOUS STATION
0
CB / Disconnector interlocking facility
I I
0 0
S S P P R R I I N N G G C C H H A A R R G G I I N N G G
I I N N S S T T R R U U C C T T I I O O N N
1 1 ) ) O O p p e e n n t t h h e e l l e e v v e e r r ' ' s s c c o o v v e e r r
2 2 ) ) I I n n s s e e r r t t t t h h e e l l e e v v e e r r n n t t o o t t s s p p l l e e c c e e
3 3 ) ) T T u u r r n n t t h h e e l l e e v v e e r r a a s s n n d d c c a a t t e e d d
b b y y t t h h e e a a r r r r o o w w , , k k e e e e p p o o n n c c h h a a r r g g n n g g
u u n n t t l l t t h h e e s s p p r r n n g g s s c c h h a a r r g g e e d d
s s n n g g s s s s e e e e n n . .
4 4 ) ) P P u u l l l l o o u u t t t t h h e e l l e e v v e e r r a a f f t t e e r r
c c h h a a r r g g n n g g a a n n d d c c l l o o s s e e t t h h e e c c o o v v e e r r
T T o o l l o o c c k k t t h h e e b b r r e e a a k k e e r r , ,
p p u u s s h h t t h h e e o o p p e e n n n n n n g g b b u u t t t t o o n n
( ( 0 0 ) ) a a n n d d t t u u r r n n t t h h e e k k e e y y
*
CB / Disconnector interlocking mechanism is always available to ensure correct operation and operation
sequence, as per IEC62271-1 and relevant standards. To close the CB the disconnector shall be closed first,
vice versa to open the disconnector the CB shall be opened first. The following steps show how to perform
that step by step. Please take that into consideration while going to operate the CB or disconnector.
Remove the key from disconnector safety lock and place it on circuit breaker. Open the CB lock and charge
the spring by the lever. If auxiliary supply voltage connection is made, charging spring will be automatically
done. Please double check its MCB position.
I I
0 0
S S P P R R I I N N G G C C H H A A R R G G I I N N G G
I I N N S S T T R R U U C C T T I I O O N N
1 1 ) ) O O p p e e n n t t h h e e l l e e v v e e r r ' ' s s c c o o v v e e r r
2 2 ) ) I I n n s s e e r r t t t t h h e e l l e e v v e e r r n n t t o o t t s s p p l l e e c c e e
3 3 ) ) T T u u r r n n t t h h e e l l e e v v e e r r a a s s n n d d c c a a t t e e d d
b b y y t t h h e e a a r r r r o o w w , , k k e e e e p p o o n n c c h h a a r r g g n n g g
u u n n t t l l t t h h e e s s p p r r n n g g s s c c h h a a r r g g e e d d
s s n n g g s s s s e e e e n n . .
4 4 ) ) P P u u l l l l o o u u t t t t h h e e l l e e v v e e r r a a f f t t e e r r
c c h h a a r r g g n n g g a a n n d d c c l l o o s s e e t t h h e e c c o o v v e e r r
T T o o l l o o c c k k t t h h e e b b r r e e a a k k e e r r , ,
p p u u s s h h t t h h e e o o p p e e n n n n n n g g b b u u t t t t o o n n
( ( 0 0 ) ) a a n n d d t t u u r r n n t t h h e e k k e e y y
Close the Circuit Breaker:
Closing can be done either manual or motorised by
pressing ON button on CB or control panel.
I I
0
0 0
!
DO NOT INTERFERE WITH THE EARTHING
MECHANISM WHILE THE LOAD BREAK
I
SPRING IS CHARGED
I
Breaker spring charging lever
Circuit Breaker ON button
Circuit Breaker OFF button
CB - Disconnector Interlocking Facility
Breaker ON button
CB - Disconnector
interlocking facility
Ulusoy HMH24-04 Incoming/Outgoing Switchgear with Circuit Breaker User Manual
I I
0 0
S S P P R R I I N N G G C C H H A A R R G G I I N N G G
I I N N S S T T R R U U C C T T I I O O N N
1 1 ) ) O O p p e e n n t t h h e e l l e e v v e e r r ' ' s s c c o o v v e e r r
2 2 ) ) I I n n s s e e r r t t t t h h e e l l e e v v e e r r n n t t o o t t s s p p l l e e c c e e
3 3 ) ) T T u u r r n n t t h h e e l l e e v v e e r r a a s s n n d d c c a a t t e e d d
b b y y t t h h e e a a r r r r o o w w , , k k e e e e p p o o n n c c h h a a r r g g n n g g
u u n n t t l l t t h h e e s s p p r r n n g g s s c c h h a a r r g g e e d d
s s n n g g s s s s e e e e n n . .
4 4 ) ) P P u u l l l l o o u u t t t t h h e e l l e e v v e e r r a a f f t t e e r r
c c h h a a r r g g n n g g a a n n d d c c l l o o s s e e t t h h e e c c o o v v e e r r
T T o o l l o o c c k k t t h h e e b b r r e e a a k k e e r r , ,
p p u u s s h h t t h h e e o o p p e e n n n n n n g g b b u u t t t t o o n n
( ( 0 0 ) ) a a n n d d t t u u r r n n t t h h e e k k e e y y
Open the Circuit Breaker:
Closing can be done either manual or motorised by
pressing OFF button on CB or control panel.
Breaker OFF button
CB - Disconnector
interlocking facility
www.eaton.com
9