Status Bytes; Table 17: Status Byte Ch1_S0; Table 18: Status Byte Ch2_S1 - WAGO I/O-SYSTEM 750 Manual

8ao 0-10v/±10v dc, 8-channel analog output module 0...10 v/±10 v
Table of Contents

Advertisement

29
Process Image
4.2

Status Bytes

The status byte for channel 1 displays the diagnoses "Undervoltage field supply"
and "General Error".

Table 17: Status Byte CH1_S0

Bit 7
RegCom
Power Supply
General Error
RegCom
The status byte for channels 2 to 8 are implemented identically and only display
the "General Error" diagnosis.
The following table describes the status byte of channel 2.

Table 18: Status Byte CH2_S1

Bit 7
RegCom
General Error
RegCom
Manual
Version 1.0.0
Status byte CH1_S0, Byte 0
Bit 6
Bit 5
Bit 4
General
Power
Error
Supply
Undervoltage field supply
0
Voltage for the field supply is adequate.
1
Voltage for the field supply is too low.
General Error
0
No error present.
1
There is a general error.
Register communication
0:
Register communication is disabled (normal mode).
1:
Register communication is enabled.
Status byte CH2_S1, Byte 3
Bit 6
Bit 5
Bit 4
General
Error
General Error
0
No error present.
1
There is a general error.
Register communication
0:
Register communication is disabled (normal mode).
1:
Register communication is enabled.
Bit 3
Bit 2
Bit 3
Bit 2
WAGO-I/O-SYSTEM 750
750-597 8AO 0-10V/±10V DC
Bit 1
Bit 1
Bit 0
Bit 0