Grounding scheme (example)
Signal ground
Minimum cable cross-section
Spray gun
AquaCoat cabinet
Reciprocator
Conveyor
Spray booth
Spraying stand
Safe operation of the AquaCoat system is only guaranteed with a grounding connection.
Connect all ground cables using a short and direct route.
Tank
All paints, flushing agents and waste tanks have to be made of metal.
All tanks in the cabinet must be connected to the potential equalization. All further
tanks must be grounded.
ORDER NUMBER DOC 2369735
Floor, static dissipative
4 mm²; AWG 12
4 mm²; AWG 12
16 mm²; AWG 6
16 mm²; AWG 6
16 mm²; AWG 6
16 mm²; AWG 6
Conveyor
R
max
< 1 MΩ
Spraying stand
B_06136
Work piece
Signal ground