ProSoft Technology ILX69-PBM User Manual page 87

Table of Contents

Advertisement

ILX69-PBM ♦ CompactLogix™ or MicroLogix™ Platform
PROFIBUS Master Communication Module
DPV1 Alarm Response
Code
86 hex = REJ_INT
87 hex = REJ_SRT The alarm handler
88 hex = REJ_ENA The alarm that
89 hex = REJ_NPD The alarm that
9a hex =
REJ_COM
ProSoft Technology, Inc.
Significance
Error source
The alarm handler
Device
is not initialized
Device
is currently stopped
Host
shall be
acknowledged is
not enabled in
slave parameter
data
Host
shall be
acknowledged is
not pending on a
MSAL1_Alarm_Re
s
Unknown msg.b
Host
command
Help
No DPV1 capable device configured within
the module
No DPV1 capable slave device is in
process data exchange with the device.
Check if network is running.
Enable the corresponding alarm in slave
configuration data set
Check the parameter AlarmType and
Seq_Nr. Both must be equal to the
MSAL1_Alarm_ind parameter
Correct the requested msg.b parameter of
message
Communication
User Manual
Page 87 of 113