Upgrading the Subsystem
4. Enter option 2. The following menu appears:
Install Options:
1. Other controller and cache module
2. Other controller module
3. Other cache module
4. Exit
Enter choice: 1, 2, 3, or 4 ->
5. Enter option 1. The following display appears:
Insert both the slot A [or B} controller and cache module? Y/N
6. Enter Y(es). The following display appears:
Quiescing all device ports. Please wait...
Device Port 1 quiesced.
Device Port 2 quiesced.
Device Port 3 quiesced.
Device Port 4 quiesced.
Device Port 5 quiesced.
Device Port 6 quiesced.
All device ports quiesced.
.
.
.
BA370 enclosure display:
Perform the following steps:
1. Turn off the battery for the new cache module by pressing
the battery's shut off button for five seconds.
2. Connect the battery to the new cache module.
3. Insert the new cache module in slot B within 4 minutes.
Model 2200 enclosure display:
Insert the new cache module in slot B within 4 minutes.
NOTE: A countdown timer allows a total of 4 minutes to install the controller and cache
module. After 4 minutes, "this controller" will exit FRUTIL and resume operations. If this
happens, return to step 2 and proceed.
5–38
HSG80 Array Controller V8.7 Maintenance and Service Guide