I/O Module Locations In A Model 2200 Enclosure - HP StorageWorks HSG80 Array Controller V8.7 Maintenance And Service Manual

Hide thumbs Also See for StorageWorks HSG80 Array Controller V8.7:
Table of Contents

Advertisement

Figure 4–10: I/O module locations in a Model 2200 enclosure
Figure 4–11: I/O module bay to SCSI bus number correlation
Use the following steps to replace any number of failed I/O modules.
1. Connect a PC or terminal to the maintenance port of an operational controller.
2. In a dual-redundant controller configuration, disable failover and take the
controllers out of their dual-redundant configuration with one of the following
commands:
SET NOFAILOVER
or
SET NOMULTIBUS_FAILOVER
3. Start FRUTIL with the following command:
RUN FRUTIL
4. Enter N(o) to the question about replacing the cache battery.
5. Enter 4 for the replace an I/O module option.
6. Enter Y(es) to confirm the intent to replace the I/O module.
HSG80 Array Controller V8.7 Maintenance and Service Guide
Replacement Procedures for Model 2200 Enclosure Elements
1
3
2
4
CXO7182A
5
1
6
2
3
4
5
6
CXO7183A
SCSI bus 1
SCSI bus 2
SCSI bus 3
SCSI bus 4
SCSI bus 5
SCSI bus 6
4–27