Appendix A: TV-VVTZC-E2 Points/Properties

NOTE Engineering units shown in this document in the defaults and ranges are strictly for reference. You must
enter an integer only.

Status

Navigation:
i-Vu® / Field Assistant:
Point Name/Description
Terminal Mode – The controller's current operating status.
Terminal Type – The type of zone terminal that the controller is installed on.
Space Temperature - Prime Variable – The space temperature value currently used for
control.
Damper Position – The current damper position.
Supply Air Temperature – Displays the current supply air temperature.
Heating Capacity – The current reheat capacity when the zone is configured for reheat.
Baseboard Heating Capacity – The current modulating baseboard heat capacity when
the zone is configured for Combination Baseboard and Ducted Heat.
Outdoor Air Temperature – The current outdoor air temperature from a linked air
source, if available, or from another network source.
Fan – The status of the terminal fan if Term Type is Parallel Fan or Series Fan.
Space Relative Humidity – The current space relative humidity if Service Configuration
> Hardwired Sensor is set to RH Sensor or, you have a valid ZS RH sensor.
Indoor Air Quality CO2 (ppm) – The current IAQ value if Service Configuration >
Hardwired Sensor is set to CO2 Sensor or, you have a valid ZS CO
Shutdown – When Active, disables all control functions, at normal equipment time
delays and close the damper.
TruVu™ VVTZC-E2
Installation and Start-up Guide
Properties
Control Program
>
2
sensor.
101
Appendix A: TV-VVTZC-E2 Points/Properties
Status
>
Range
R:
Off
Heating
Warm-up
Vent
Cooling
Dehumidify
Reheat
Pressurize
Evacuate
Shutdown
IAQ Override
Air Balancing
R:
Single Duct
Parallel Fan
Series Fan
R:
-56 to 245°F
(-48.9 to 118.3°C)
R:
0 to 100%
R:
-56 to 245°F
(-48.9 to 118.3°C)
R:
0 to 100%
R:
0 to 100%
R:
-56 to 245°F
(-48.9 to 118.3°C)
R:
On/Off
R:
0 to 100%rh
R:
0 to 5000ppm
D:
Inactive
R:
Inactive/Active
©2022 Carrier.
All rights reserved.