Optional) Combining The Power Cabinet And Bypass Cabinet (400 Kva, 500 Kva, Or 600 Kva Ups) - Huawei UPS5000-E-400K-SM User Manual

Hide thumbs Also See for UPS5000-E-400K-SM:
Table of Contents

Advertisement

UPS5000-E-(350 kVA-800 kVA)
User Manual (50 kVA Power Modules)
Figure 3-18 Removing connecting plates
Step 8 Use a manual pallet truck to transport the power cabinet and bypass cabinet to the installation
position. Ensure that the two cabinets align with each other.
----End
3.1.6 (Optional) Combining the Power Cabinet and Bypass
Cabinet (400 kVA, 500 kVA, or 600 kVA UPS)
Procedure
Step 1 Install the bottom, middle, and top connecting plates for the power cabinet and bypass cabinet
based on screw specifications in
Step 2 Install the removed soft copper bars and battery copper bar components based on their
numbers by referring to screw specifications in
Step 3 Reconnect the removed cables to the system signal interface board in the power cabinet, and
bind the cables. For details, see
Step 4 Check that the power cabinet and bypass cabinet are combined completely and securely.
Step 5 After checking that cabinets are combined properly, reinstall the side covers and rear covers.
----End
Issue 05 (2018-01-08)
Table 3-6
Table
3-8.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
and
Table
3-7.
Table 3-6
and
Table
3 Installation
3-7.
74