UPS5000-E-(350 kVA-800 kVA)
User Manual (50 kVA Power Modules)
Procedure
Step 1 On the main screen of the LCD, tap System Info. Tap
displayed.
Step 2 On the Maintenance screen, tap Battery Maint..
Figure 5-18 Maintenance
Step 3 Tap Start next to Forced Equalized Charging to start a forced equalized charging test.
Figure 5-19 Starting a forced equalized charging test
Issue 05 (2018-01-08)
The mains input is normal.
Batteries are properly connected.
Batteries are not in the equalized charging state.
The forced equalized charging test automatically stops in any of the following cases:
The forced equalized charging test duration reaches the forced equalized charging protection time
(12–24 h, 18 h by default).
The UPS generates a battery overtemperature, overvoltage, or overcurrent alarm.
An alarm is generated.