Initial Startup - Huawei UPS5000-E-400K-SM User Manual

Hide thumbs Also See for UPS5000-E-400K-SM:
Table of Contents

Advertisement

UPS5000-E-(350 kVA-800 kVA)
User Manual (50 kVA Power Modules)
Default User
operator (common user)
browser (browsing user)

5.1.2.1 Initial Startup

Step 1 After the MDU starts properly, set the language, time and date, network parameters, and
system parameters on the Settings Wizard screen.
Set system parameters with caution because the settings determine normal UPS operation.
Battery parameter settings are critical to battery maintenance, battery lifespan, and UPS
discharge time. When you set battery parameters, note the following:
Issue 05 (2018-01-08)
Set Single/Parallel after double check. Incorrect setting may affect the normal UPS
operation.
Output voltage level refers to the line voltage level. Set it based on site requirements.
Set Output frequency correctly; otherwise, loads may be affected and the UPS may not
work properly.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Preset Password
WebUI
LCD
WebUI
WebUI
5 Operations
Changeme
000001
Changeme
-
237