Battery Specifications; Output Electrical Specifications - Huawei UPS5000-E-400K-SM User Manual

Hide thumbs Also See for UPS5000-E-400K-SM:
Table of Contents

Advertisement

UPS5000-E-(350 kVA-800 kVA)
User Manual (50 kVA Power Modules)
Item
voltage
Rated
frequency
Input
frequency
Input system

8.7 Battery Specifications

Item
Battery voltage
Battery
management
One-button
cold start
Battery string
sharing
Charge voltage

8.8 Output Electrical Specifications

Item
Output system
Voltage
Frequency
Issue 05 (2018-01-08)
400 kVA
500 kVA
50 Hz or 60 Hz
± 6 Hz (adjustable, 0.5–6 Hz, ± 2 Hz by default)
The mains input and bypass input can share a power source or use different
power sources.
400 kVA
500 kVA
360–528 V DC (12 V batteries, 30–44 batteries, 40 by default); If there
are 36–44 batteries, output power is not derated. If there are 34 batteries,
output power is derated to 0.9. If there are 32 or 30 batteries, output
power is derated to 0.8.
Intelligent battery management
In the case of a mains failure, batteries can start the UPS to power loads.
Battery string sharing is supported in a parallel system. No battery string
is shared by default.
Equalized voltage: 2.3–2.4 V/Cell, default: 2.35 V/Cell (30–42
batteries)
Equalized voltage: 2.3–2.35 V/Cell, default: 2.35 V/Cell (44
batteries)
Float voltage: 2.23–2.3 V/Cell, default: 2.25 V/Cell (30–44 batteries)
400 kVA
Three-phase, four-wire, and PE
380 V AC, 400 V AC, or 415 V AC (tolerance ± 1%) (line voltage)
In normal mode, the mains frequency is synchronous with the
bypass input frequency.
In battery mode, the frequency is 50 Hz or 60 Hz (tolerance
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
600 kVA
600 kVA
500 kVA
600 kVA
8 Technical Specifications
800 kVA
800 kVA
800 kVA
281