UPS5000-E-(350 kVA-800 kVA)
User Manual (50 kVA Power Modules)
Figure 5-10 BCB connection setting
----End

5.2 Shutting Down and Powering Off the UPS

Context
After the inverter is shut down, if the bypass is normal, the UPS transfers to bypass mode; if
the bypass is not normal, the UPS supplies no power. Before shutting down the UPS, ensure
that all loads have shut down.
Procedure
Step 1 Shut down the inverter.
Issue 05 (2018-01-08)
On the LCD
a.
On the main screen, tap Common Functions. Tap Inv. OFF.
b.
If no user is logged in, enter a user name and password, and tap
login screen displayed.
c.
In the displayed dialog box, tap Yes to shut down the inverter.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
5 Operations
on the
247