2.4 Typical configurations

Table 2-13 Typical UPS configurations
Configuration

Single UPS

Parallel system
Dual-bus system
2.4.1 Single UPS
This series uses a modular design in which multiple power modules are connected in parallel
to deliver a high loading capacity. If a single power module is faulty, the other power modules
continue working. When the load power is small, even a single UPS can provide redundant
capacity, which ensures high reliability.
Issue 05 (2018-01-08)
Port Name
Application Scenario
Supplies power to common loads.
Supplies power to important loads in small- and medium-sized data
centers. It features high availability and strong transient overload
capability.
The dual-bus system is suitable for scenarios where high availability
requirements are posed for power supply. The dual-bus system
supplies power to important loads in large- and medium-sized
equipment rooms and data centers.
In addition to common parallel system advantages, the dual-bus
system also provides outstanding availability and eliminates
bottleneck failures. However, configuration of the dual-bus system is
complex.
A 1+1 parallel system is a typical configuration. You can set the number of requisite UPSs and
redundant ones on the LCD or WebUI.