4.2.6.2 RCCMD Event Shutdown and Message Sending

Procedure
Step 1 On the RCCMD client, choose Connections, add the server IP address, and set the encryption
mode to encryption.
Figure 4-107 Setting the MDU IP address and SSL encrypted transmission mode on the RCCMD
client
Step 2 On the MDU WebUI, choose Config. > RCCMD, and set RCCMD function to Enable. For
details, see
Step 3 On the WebUI of the MDU, the SSL encryption is set to Enable by default and does not need
to be set. If the RCCMD client is set to the unencrypted mode, you need to set the SSL
encryption to Disable on the server WebUI.
Step 4 Configure events. If you set the job type to RCCMD Message under Inverter on, specify the
IP address and port of the RCCMD client. The port is 6003 by default. If you need to modify
the port, modify the port on the RCCMD client at the same time to keep them the same. Enter
the message to be sent and set the message sending mechanism. For example, set it to
Immediately, once.
Issue 05 (2018-01-08)
If encryption is disabled, you do not need to select the encrypted transmission.
All configurations take effect only after restart.