UPS5000-E-(350 kVA-800 kVA)
User Manual (50 kVA Power Modules)
UPS
UPS5000-E-50
0K-FM
UPS5000-E-60
0K-SM
UPS5000-E-60
0K-FM
UPS5000-E-80
0K-SM
UPS5000-E-80
0K-FM

8.3 Environment Parameters

Environment
Feature
Operating
temperature
Storage
temperature
Relative
humidity
Altitude

8.4 Safety Regulations and EMC

Safety and
EMC
Safety
regulations
EMC
Issue 05 (2018-01-08)
Maintenance
Mains input
bypass switch
switch
1000 V AC/800
1000 V
A/3P
AC/1000 A/3P
1000 V
-
AC/1000 A/3P
1000 V
1000 V
AC/1000 A/3P
AC/1250 A/3P
1000 V
-
AC/1250 A/3P
1000 V
1000 V
AC/1250 A/3P
AC/1600 A/3P
400 kVA
500 kVA
0–40° C
–40° C to +70° C
0%–95% RH (non-condensing)
0–1000 m
When the altitude is greater than 1000 m and less than 4000 m, the rated
power should be derated. For details, see the IEC62040-3.
400 kVA
500 kVA
EN62040-1: 2013
IEC62040-1: 2013
YD/T2165-2010
EN62040-2
IEC62040-2
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
8 Technical Specifications
Bypass input
Output
switch
switch
1000 V AC/800
1000 V AC/800
A/3P
A/3P
-
-
1000 V
1000 V
AC/1000 A/3P
AC/1000 A/3P
-
-
1000 V
1000 V
AC/1250 A/3P
AC/1250 A/3P
600 kVA
800 kVA
600 kVA
800 kVA
279