Table 5-2 Battery parameter setting example
Battery
Specifications
150 Ah/12 V
300 Ah/2 V
300 Ah/12 V
300 Ah/2 V
Step 2 After you set parameters on the Settings Wizard screen, the MDU displays the Bypass mode
and No battery alarms, which do not need to be handled. If there is any other alarm, you need
to rectify the fault.
If dry contact signals are connected to the system, choose System Info > Settings > Dry contacts and
check that the connected dry contacts have been enabled and that the disconnected dry contacts have
been disabled.
Step 3 View the system running diagram on the MDU to check that the UPS is working in bypass
mode.
----End
Issue 05 (2018-01-08)
After you set network parameters, connect the UPS to the network over a network cable, which
enables you to remotely manage the UPS. If you do not need remote management, retain the default
network parameter settings.
Number of
Batteries
36 batteries in
series
192 batteries in
series
40 batteries in
series
240 batteries in
series
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Number of
Number of
Battery
Cells
Strings
Two battery
36 x 6 = 216
strings
connected in
parallel
Two battery
192 x 1 = 192
strings
connected in
parallel
Three battery
40 x 6 = 240
strings
connected in
parallel
Four battery
240 x 1 = 240
strings
connected in
parallel
5 Operations
Battery
Capacity
150 Ah + 150
Ah = 300 Ah
300 Ah + 300
Ah = 600 Ah
300 Ah + 300
Ah + 300 Ah =
900 Ah
300 Ah + 300
Ah + 300 Ah +
300 Ah = 1200
Ah
239