Step 7 Remove the top, middle, and bottom connecting kits in sequence from the power
cabinet and bypass cabinet.
Use a step ladder to remove the top connecting kits as the cabinet is high.
Figure 3-14 Removing connecting kits
Step 8 Use a manual pallet truck to transport the power cabinet and bypass cabinet to
the installation position. Ensure that the two cabinets align with each other.
----End
3.1.8 (Optional) Combining the Power Cabinet and Bypass
Cabinet (300K-FT, 400K, 500K, 600K)
Procedure
Step 1 Reinstall the bottom, middle, and top connecting kits for the power cabinet and
bypass cabinet based on screw specifications, screw quantity, and recorded
information.
Issue 05 (2020-04-27)
NO TE
For a 500K or 600K UPS, remove the soft copper bars numbered 48–54.
NO TICE
Copyright © Huawei Digital Power Technologies Co., Ltd.
3 Installation
82