Huawei UPS5000-E-400K-SM User Manual

Hide thumbs Also See for UPS5000-E-400K-SM:
Table of Contents

Advertisement

Quick Links

UPS5000-E-(350 kVA-800 kVA)
User Manual (50 kVA Power
Modules)
Issue
05
Date
2018-01-08
HUAWEI TECHNOLOGIES CO., LTD.

Advertisement

Table of Contents
loading

Summary of Contents for Huawei UPS5000-E-400K-SM

  • Page 1 UPS5000-E-(350 kVA-800 kVA) User Manual (50 kVA Power Modules) Issue Date 2018-01-08 HUAWEI TECHNOLOGIES CO., LTD.
  • Page 2 Notice The purchased products, services and features are stipulated by the contract made between Huawei and the customer. All or part of the products, services and features described in this document may not be within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements, information, and recommendations in this document are provided "AS IS"...
  • Page 3: About This Document

    Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 4 Issue 03 (2017-04-28) Update some MDU screenshots. Issue 02 (2017-02-25) Updated the voltage and current data of the monitoring interface card. Issue 01 (2016-10-14) This is the first release. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 5: Table Of Contents

    2.3.5.3 Dry contact card ..............................35 2.3.5.4 Monitoring interface card ............................. 37 2.3.6 MDU ..................................43 2.4 Typical configurations ..............................45 2.4.1 Single UPS ................................45 2.4.2 Parallel System ................................ 46 Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 6 3.2.7.1 Top Cable Routing .............................. 125 3.2.7.2 Bottom Cable Routing ............................133 3.2.8 Remote EPO ................................141 3.2.9 Connecting Communications Cables ........................142 3.3 Parallel System Installation ............................143 Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 7 4.2.6.2 RCCMD Event Shutdown and Message Sending ....................232 4.2.6.3 UPS Alive Check Function ..........................233 5 Operations ..........................236 5.1 Powering On and Starting the UPS ........................... 236 Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 8 8 Technical Specifications ......................278 8.1 Physical Parameters ..............................278 8.2 Internal Switch Parameters ............................278 8.3 Environment Parameters ............................279 8.4 Safety Regulations and EMC ............................ 279 Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 9 B Menu Hierarchy ........................285 B.1 Menus on the LCD ..............................285 B.2 Menus on the WebUI..............................287 C Alarm List ..........................304 D Acronyms and Abbreviations....................317 Issue 05 (2018-01-08) Huawei Proprietary and Confidential viii Copyright © Huawei Technologies Co., Ltd.
  • Page 10: Safety Precautions

    Follow the precautions and special safety instructions provided by Huawei when operating Huawei products. Huawei will not be liable for any consequences that are caused due to violations regarding general safety regulations and equipment design, production, and usage safety standards.
  • Page 11 Personal Requirements Only Huawei engineers or engineers certified by Huawei are allowed to perform UPS commissioning and maintenance. Otherwise, human injury or equipment damage may occur, and any resulting UPS faults will be beyond warranty scope.
  • Page 12: Electrical Safety

     Never use water to clean electrical components inside or outside the UPS.  Do not drill holes into a cabinet. 1.2 Electrical Safety High Voltage Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 13 Otherwise, electric shocks may occur.  Before installing or removing the power cable, open the power switch.  Before connecting a power cable, check that its label is correct. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 14 Package boards with ESD packaging materials before storing or transporting them. Figure 1-1 shows how to wear an ESD wrist strap. Figure 1-1 Wearing an ESD wrist strap Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 15: Operating Environment

    1.4 Battery Safety This section describes precautions for operating batteries. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 16  To ensure battery safety and efficient battery management, use the batteries delivered with the UPS. Huawei shall not be responsible for battery damage caused by using non-Huawei batteries for Huawei UPSs. ...
  • Page 17 If any personnel are exposed to battery electrolyte, wash the exposed area with clean water immediately and seek medical advice if the situation is serious. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 18: Mechanical Safety

     Move the cabinet with caution. Any bumping or falling may damage the device. Figure 1-2 Tilting angle of a cabinet Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 19: Laying Out Cables

    The air exhaust vent should not be blocked by any object. Before connecting a cable, ensure that the cable and cable label to be used meet the actual installation requirements. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 20: Overview

    Table 2-1 Model number details Item Description Product UPS, short for uninterruptible power system category UPS family 5000 E series subcategory Output  400K: The output capacity is 400 kVA. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 21: Working Principle

     FM: full configuration  The UPS5000-E-400K-SM/FM uses 50 kVA power modules. It can expand up to 400 kVA and is compatible downwards to 50 kVA. This document describes the 400 kVA UPS.  The UPS5000-E-500K-SM/FM uses 50 kVA power modules. It can expand up to 500 kVA and is compatible downwards to 50 kVA.
  • Page 22: Working Modes

    In normal mode, the rectifier converts AC power into DC power, then the inverter converts DC power into high-precision AC outputs. The conversions protect loads from interference such as input harmonics, glitches, and voltage transients. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 23: Bypass Mode

    The bypass power supply is not protected by the UPS which means it may be affected by mains outage, and incorrect AC voltage or frequency. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 24: Battery Mode

    If the mains input is abnormal or the rectifier becomes abnormal, the UPS transfers to battery mode. The power module obtains DC power from batteries, and the power is converted into AC output by the inverter. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 25: Maintenance Bypass Mode

    When the UPS works in maintenance bypass mode, the current flows through the maintenance bypass instead of the power module. You can maintain the circuit inside the cabinet. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 26: Eco Mode

    ECO voltage range, the UPS transfers from bypass mode to normal mode. In bypass mode or normal mode, the rectifier keeps working and charges batteries using a charger. The ECO mode delivers a high efficiency. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 27: Product Introduction

    Manual startup is required to ensure that the inverter is in standby state and the power flow has reached the inverter. 2.3 Product Introduction 2.3.1 Appearance Figure 2-8 Figure 2-10 show the 400 kVA, 500 kVA, 600 kVA, and 800 kVA UPSs. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 28 User Manual (50 kVA Power Modules) 2 Overview Figure 2-8 400 kVA/500 kVA UPS (1) Power (2) Anchor baffle (3) Monitor display unit (4) Bypass cabinet plates (MDU) cabinet Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 29 UPS5000-E-(350 kVA-800 kVA) User Manual (50 kVA Power Modules) 2 Overview Figure 2-9 600 kVA UPS (1) Power cabinet (2) Anchor baffle plates (3) MDU (4) Bypass cabinet Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 30: Product Structure

    (4) MDU (5) Bypass cabinet 2 (6) Bypass cabinet 1 2.3.2 Product Structure Figure 2-11 Figure 2-18 show the structures of UPSs with the front doors open. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 31 Figure 2-11 Product structure (400 kVA in standard configuration) (1) Power modules (2) Control module (3) Power distribution module cover (4) Maintenance bypass switch (5) Bypass module Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 32 (1) Power modules (2) Control module (3) Power distribution module cover (4) Maintenance bypass (5) Bypass module (6) Mains input switch switch (7) Output switch (8) Bypass input switch Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 33 Figure 2-13 Product structure (500 kVA in standard configuration) (1) Power modules (2) Control module (3) Power distribution module cover (4) Maintenance bypass switch (5) Bypass module Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 34 (1) Power modules (2) Control module (3) Power distribution module cover (4) Maintenance bypass (5) Bypass module (6) Mains input switch switch (7) Output switch (8) Bypass input switch Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 35 Figure 2-15 Product structure (600 kVA in standard configuration) (1) Power modules (2) Control module (3) Power distribution module cover (4) Maintenance bypass switch (5) Bypass module Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 36 (1) Power modules (2) Control module (3) Power distribution module cover (4) Maintenance bypass (5) Bypass module (6) Mains input switch switch (7) Output switch (8) Bypass input switch Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 37 Figure 2-18 Product structure (800 kVA in full configuration) (1) Power modules (2) Control module (3) Maintenance bypass switch (4) Power distribution module (5) Bypass module (6) Mains input switch cover Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 38: Power Module

    (blinking at 0.5 Hz, on for 1s and off for 1s).  The inverter is not started (blinking at 0.2 Hz, on for 2.5s Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 39: Bypass Module

    Power density: 50 kVA/3 U 2.3.4 Bypass Module Appearance 400 kVA/500 kVA/600 kVA bypass module have the same appearance. Figure 2-20 shows the 600 kVA bypass module. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 40 Figure 2-21 800kVA bypass module (1) Positioning (2) Cold start (3) Run (4) Alarm indicator lock button indicator (5) Fault indicator (6) Ready switch (7) Crowbar (8) Auxiliary power supply Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 41 400 kVA/500 kVA/600 kVA: 600 mm x 200 mm x 600 mm 800 kVA: 500 mm x 480 mm x 550 mm −  Weight − 400 kVA/500 kVA/600 kVA: 50 kg Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 42: Control Module

    Ports are protected by a security mechanism. 2.3.5.2 ECM Appearance The control module consists of two energy control modules (ECMs) in active/standby mode. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 43 ECM is being upgraded. FAULT Steady on The ECM has a critical alarm. The ECM has no critical alarm or the DSP of the ECM is being upgraded. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 44: Dry Contact Card

    CAN communication, and inter-rack parallel CAN communication. Figure 2-24 Logical connections for CAN communication Specifications  Hot-swappable  1 U high 2.3.5.3 Dry contact card Appearance Figure 2-25 Dry contact card Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 45 ON  Disconnected: circuit breaker SWITCH Port for signal ground STATUS_ SWITCH Port for monitoring the  Disconnected: Disconnected STATUS_ maintenance circuit breaker circuit breaker ON Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 46: Monitoring Interface Card

    The dry contact card allows the UPS to detect and manage the switch status of the battery system (including the external battery switch) and implement remote emergency power-off (EPO). Specifications  Hot-swappable  0.5 U high 2.3.5.4 Monitoring interface card Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 47 DO_2 DO_2 is used to output alarms and indicates minor alarms by default. It can be set to indicate critical alarms, bypass mode, Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 48 0.5–1.5 mm  RS485 cables and FE cables must be shielded cables. Figure 2-27 Figure 2-28 are recommended wiring methods for DO ports. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 49 User Manual (50 kVA Power Modules) 2 Overview Figure 2-27 Wiring method 1 Figure 2-28 Wiring method 2 Figure 2-29 COM1 pins Table 2-8 COM1 pin definition Description RS485– RS485+ Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 50 UPS5000-E-(350 kVA-800 kVA) User Manual (50 kVA Power Modules) 2 Overview Description 12V_PORT Figure 2-30 COM2 pins Table 2-9 COM2 pin definition Description RS485+ RS485– RS485+ RS485– CANH0 CANL0 Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 51 Connect pins 1, 2, 4, and 5. Twist cables to pin 1 and pin 4 into one cable and then connect it to RS485+. Twist cables to pin 2 and pin 5 into one cable and then connect it to RS485–. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 52: Mdu

    Color Meaning A critical alarm has been generated, and the buzzer sounds continuously. Yellow A minor alarm has been generated, and the buzzer buzzes at 2 Hz. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 53 LCD online and upgrading configurations Restart switch for the MDU Reserved DIP switch Implements specific functions by using the DIP switch and specific buttons; controls the CAN Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 54: Typical Configurations

    If a single power module is faulty, the other power modules continue working. When the load power is small, even a single UPS can provide redundant capacity, which ensures high reliability. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 55: Parallel System

    An optional static transfer switch (STS) can be installed to start the bus synchronization controller (BSC). The UPS systems work in normal mode or bypass mode. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 56: Optional Components

     PDU8000-2000DCV8-BGA kVA, 600 kVA 800 kVA PDU8000-2000DCV8-BGA001 Ensures heat dissipation. For air-flow details, see the document cabinet delivered with the top air-flow cabinet. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 57 Parallel 5 m/10 m/15 m Connects UPSs in parallel. cable 5 m/10 m/15 m/60 m Transmits bus synchronization cable signals in a dual-bus system. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 58 If an IP21 component is installed, cables cannot be routed from the top of the cabinet.  The ECM extended subrack does not support onsite installation. If this component is required, inform Huawei before purchasing the UPS to receive pre-installation services. Issue 05 (2018-01-08) Huawei Proprietary and Confidential...
  • Page 59: Installation

    UPS5000-E-(350 kVA-800 kVA) User Manual (50 kVA Power Modules) 3 Installation Installation 3.1 Installation Preparations 3.1.1 Site 3.1.1.1 UPS Dimensions Figure 3-1 Dimensions (400 kVA/500 kVA, unit: mm) Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 60 UPS5000-E-(350 kVA-800 kVA) User Manual (50 kVA Power Modules) 3 Installation Figure 3-2 Dimensions (600 kVA, unit: mm) Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 61: Installation Environment

    If a top air-flow cabinet is deployed, the UPS can be installed against a wall and no space needs to be reserved at the rear (except the 800 kVA UPS). If no top air-flow cabinet is Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 62: Tools And Instruments

    Prepare the following tools and meters indicated in Table 3-1 for installation. Table 3-1 Tools and meters Tools and Meters Electric pallet truck Manual pallet truck Ladder Rubber mallet Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 63 Cotton cloth Label Electrician's knife (PVC) insulation tape Electrostatic Protective gloves Insulated gloves Insulation protective discharge (ESD) shoes gloves Torque screwdriver Cable cutter Brush Flat-head screwdriver (2–5 mm) Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 64: Power Cables

    2 x (4 x 185) 2 x (4 x 240) 3 x (4 x 185) 3 x (4 x 185) 3 x (4 x 240) conn nded ector cross-secti onal area Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 65 4 x (4 x 185) 4 x (4 x 240) 4 x (4 x 240) 4 x (4 x 240) 4 x (4 x 240) conn nded ector cross-secti onal area Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 66 The maximum battery discharge current refers to the current when forty 12 V batteries in standard configuration, that is, two hundred and forty 2 V battery cells (1.67 V/cell), stop discharging. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 67 47 N· m terminals connector Table 3-5 Recommended input front-end and output back-end circuit breakers UPS Capacity Component Specifications 350 kVA Mains input circuit breaker 800 A/3P Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 68 Bypass input circuit breaker 1250 A/3P Output branch circuit 1250 A/3P breaker 750 kVA Mains input circuit breaker 1600 A/3P Bypass input circuit breaker 1250 A/3P Output branch circuit 1250 A/3P Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 69: Transportation And Unpacking

    Step 1 Visually inspect the UPS appearance for shipping damage. If any damage is found, report it to the carrier immediately. Step 2 Use a pallet truck to move the power cabinet and bypass cabinet near the installation position. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 70 (2) Place for inserting the forks of a manual pallet truck pallet truck Step 3 Cut off and remove the binding tapes, as shown in Figure 3-6. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 71 Figure 3-7. Figure 3-7 Removing the packing materials and foam Step 5 Remove the plastic bag and take out the fitting box. Store them for future use. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 72: Removing A Wooden Case (600 Kva Ups)

    Check that the fittings comply with the packing list. If some fittings are missing or do not comply with the packing list, record the information and contact your local Huawei office immediately. Step 7 Remove the screws that secure the cabinet and pallet, as shown in Figure 3-8.
  • Page 73 Figure 3-9 Pallet (1) Inserting position of forks Step 3 Remove the barrier chips around the cabinet packing materials, as shown in Figure 3-10. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 74 UPS5000-E-(350 kVA-800 kVA) User Manual (50 kVA Power Modules) 3 Installation Figure 3-10 Removing barrier chips Step 4 Remove the packing materials and foam, as shown in Figure 3-11. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 75 Check that the fittings comply with the packing list. If some fittings are missing or do not comply with the packing list, record the information and contact your local Huawei office immediately. Step 8 Remove the screws that secure the cabinet and pallet, as shown in Figure 3-12.
  • Page 76: Optional) Splitting The Power Cabinet And Bypass Cabinet (400 Kva, 500 Kva, Or 600 Kva Ups)

    Put away the removed screws and connecting plates to facilitate future cabinet combination. Table 3-6 Table 3-7 list the specifications and number of screws to be removed. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 77 Step 1 Open the front door of the bypass cabinet and remove the covers of the power distribution subrack. The covers of the power distribution subrack can be removed from the bypass cabinet only when all switches are OFF. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 78 Step 3 Remove the cable terminals that connect the system signal interface board in the power cabinet to the bypass cabinet. Disconnect cables by referring to Figure 3-14 Table 3-8, and cut off the cable ties on the disconnected cables. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 79 CT cable W309_J26 Switch cable SW1_J27 SW2_J28 SW4_J30 Because the switch extension rod is sharp, exercise caution when removing the connecting copper bars to prevent personal injury. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 80 Figure 3-15 Removing soft copper bars numbered 43, 44, and 45 For a 500 kVA or 600 kVA UPS, remove the soft copper bars numbered 56, 58, and 60. Step 5 Remove the battery copper bar component. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 81 UPS5000-E-(350 kVA-800 kVA) User Manual (50 kVA Power Modules) 3 Installation Figure 3-16 Removing the battery copper bar component Step 6 Remove the soft copper bars numbered 39–42. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 82 Step 7 Remove the top, middle, and bottom connecting plates in sequence from the power cabinet and bypass cabinet. Use a step ladder to remove the top connecting plates as the cabinet is high. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 83: Optional) Combining The Power Cabinet And Bypass Cabinet (400 Kva, 500 Kva, Or 600 Kva Ups)

    Step 4 Check that the power cabinet and bypass cabinet are combined completely and securely. Step 5 After checking that cabinets are combined properly, reinstall the side covers and rear covers. ----End Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 84: Single Ups Installation

    The marking-off template is delivered with the UPS. Procedure Step 1 Determine the cabinet installation positions on the ground based on holes in the marking-off template for ground installation. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 85 Step 2 Use a hammer drill to drill holes for installing expansion bolts, and install expansion sleeves in the holes. Figure 3-22 shows expansion bolt composition. Figure 3-23 shows how to install an expansion bolt. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 86 Partially tighten the expansion bolt. Remove the bolt, spring washer, and flat washer. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 87 Step 5 Install the front, rear, left, and right anchor baffle plates. The installation methods for different UPS models are the same. Figure 3-25 shows how to install anchor baffle plates for a 400 kVA UPS cabinet. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 88 Figure 3-26 Installing a lock for the maintenance bypass switch (400 kVA UPS, 500 kVA UPS) Figure 3-27 Installing a lock for the maintenance bypass switch (600 kVA UPS) ----End Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 89: Installing The Ups On Channel Steel

    A: mounting holes on the channel steel  B: mounting holes on the floor Figure 3-28 Mounting hole dimensions for the 400 kVA UPS and 500 kVA UPS (unit: mm) Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 90: Installing A Ups (800 Kva)

    Step 1 Determine the cabinet installation positions on the ground based on holes in the marking-off template for ground installation.  A: mounting holes on the channel steel  B: mounting holes on the floor Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 91 Knock the expansion bolt into the hole until the expansion sleeve completely fits into the hole. The expansion sleeve must be completely buried under the ground to facilitate subsequent installation. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 92  If holes are drilled for connecting routing cables at the top copper bar of the cabinet, attach grommet strips on the Grommet hole edges to protect Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 93 Step 4 Use M12x60 expansion bolts to secure the cabinets to the expansion bolt holes on the ground. Figure 3-34 shows how to secure the power cabinets. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 94 Step 6 Remove the front covers of the power distribution subrack from the bypass cabinets, as shown Figure 3-36. The front covers of the power distribution subrack can be removed only when all the switches are OFF. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 95 When reinstalling the switch extension rod, keep the dowel level, as shown in Figure 3-37. Insert the switch extension rod to the blue mark, put washers, and tighten the slotted screw to reinstall the switch extension rod. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 96 Cut off the cable ties bound between holes in soft copper bars numbered 23, 24, 25, 26, and 30. Secure the soft copper bars numbered 23, 24, 25, 26, and 30 using M12x45 screws, as shown in Figure 3-38. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 97 Remove filler panels from power cabinet 1. Take out two soft copper bars numbered 52 from the fittings, and secure them to power cabinet 1 and its adjacent bypass cabinet respectively, as shown in Figure 3-39. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 98 3-40. The mapping between the cables in the bypass cabinets and the ports on the system signal interface board is listed in Table 3-10. Figure 3-41 shows cable connections for combined cabinets. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 99 (output switch, maintenance bypass switch, and bypass input switch). The following figure describes how to connect cables for combined cabinets using a full configuration model as an example. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 100: Installing The Ups On Channel Steel

    Step 1 Determine the cabinet installation positions on the channel steel based on holes in the marking-off template for channel steel installation.  A: mounting holes on the channel steel  B: mounting holes on the floor Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 101: Installing Batteries

    Step 1 Use common M12x45 bolts to secure the cabinets into the mounting holes in the channel steel and tighten the bolts. Step 2 Install the front, rear, left, and right anchor baffle plates. ----End 3.2.3 Installing Batteries Context Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 102: Installing Optional Components

    Install antiseismic kits only when the cabinet is ground-mounted. Step 1 Mark mounting holes on the ground based on the marking-off templates. Figure 3-43 Figure 3-45 show the dimensions of antiseismic kit mounting holes. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 103 User Manual (50 kVA Power Modules) 3 Installation Figure 3-43 Dimensions of antiseismic kit mounting holes for the 400 kVA UPS and 500 kVA UPS (unit: mm) Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 104 Figure 3-44 Dimensions of antiseismic kit mounting holes for the 600 kVA UPS (unit: mm) Figure 3-45 Dimensions of antiseismic kit mounting holes for the 800 kVA UPS (unit: mm) Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 105 Step 6 Use expansion bolts to firmly lock the front and rear antiseismic kits to the ground. The installation methods for different UPS models are the same. Figure 3-48 shows how to lock antiseismic kits for a 600 kVA UPS. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 106: Installing An Ip21 Component

    Select the mounting holes for leveling feet based on the cabinet width onsite. Figure 3-49 Installing leveling feet Step 2 Secure the IP21 component to the top of each cabinet using four M12 screws. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 107: Connecting An Ambient T/H Sensor

    Step 1 Connect the RJ11 port on the ambient T/H sensor to the COM1 port on the monitoring interface card. Figure 3-51 Connecting a UPS and an ambient T/H sensor The ambient T/H sensor can be used as a battery temperature sensor. ----End Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 108: Connecting The Bcb Box

    3.2.4.6 Installing a Battery Grounding Failure Detector Procedure Step 1 Install a battery grounding failure detector. For the installation method, see UPS Battery Grounding Failure Detector User Manual. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 109 User Manual (50 kVA Power Modules) 3 Installation Figure 3-52 Position of a battery grounding failure detector in the 400 kVA, 500 kVA, or 600 kVA (1) Battery grounding failure detector Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 110: Connecting The Ibat

    Step 1 Connect the COM_OUT port on the CIM of the iBAT to the COM2 port on the monitoring interface card. For details, see iBAT 2.0-CIM01C2 Quick Guide. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 111: Ups Cable Connection Reference

    Step 3 Pull the marked cable out of the cabinet, cut the cable from the marked position, strip the cable, and crimp a terminal. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 112: Routing Cables (400 Kva, 500 Kva, Or 600 Kva Ups)

    Cables are connected in the same way for the 400 kVA, 500 kVA, and 600 kVA UPS. This section describes how to connect cables for the 400 kVA UPS. Figure 3-56 Figure 3-57 show power cable terminals. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 113 3 Installation Figure 3-56 Power distribution module (400 kVA UPS, 500 kVA UPS) (1) Mains input (2) Battery input (3) Output terminal (4) Bypass input terminal terminal terminal Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 114 Procedure Step 1 Open the front door of the bypass cabinet and remove the covers of the power distribution subrack, as shown in Figure 3-58. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 115 Step 2 Remove the covers from the top of the cabinet, drill holes in the covers for the power cables and battery cables, attach grommet strips to the hole edges for protecting cables, and reinstall the covers. The hole diameter and quantity are for reference only. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 116 (Optional) If copper bar protective covers are installed for the bypass cabinet, remove the protective covers and then the connecting copper bars. The protective covers need to be reinstalled after the connecting copper bars are removed. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 117 UPS5000-E-(350 kVA-800 kVA) User Manual (50 kVA Power Modules) 3 Installation Figure 3-60 Removing the copper bar protective covers at the rear Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 118 Figure 3-61 Removing the connecting copper bars Step 5 Connect a ground cable to the UPS. If you do not ground the UPS as required, electromagnetic interference, electric shocks, or fire may occur. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 119  Connect input power cables to the UPS and then to customer equipment. Figure 3-62 Ground cable Step 6 Connect the mains input power cables. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 120 Step 7 Connect the output power cables. After you connect output power cables, if loads are not ready to be powered, insulate the end of the system output power cable. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 121 Figure 3-64 Connecting AC output power cables Step 8 Connect the bypass input power cables. (Perform this step only when the mains input and bypass input use different power sources.) Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 122 UPS5000-E-(350 kVA-800 kVA) User Manual (50 kVA Power Modules) 3 Installation Figure 3-65 Connecting the bypass input power cables Step 9 Connect the battery cables. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 123 Take a battery string consisting of 40 batteries for example. The battery neutral wire is routed from the middle of positive and negative battery strings, each consisting of 20 batteries. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 124 Step 10 Route signal cables. Bind cables to the cabinet. Figure 3-68 shows the signal cables routed from the top of the cabinet. Bind signal cables and power cables separately. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 125: Bottom Cable Routing

    After connecting cables, check that a certain clearance is reserved between the internal switch (if any) extension pole and power cables to avoid friction. 3.2.6.2 Bottom Cable Routing Context Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 126 Step 2 Remove the cable covers from the bottom of the cabinet, drill holes in the covers, attach grommet strips to the hole edges for protecting cables, and reinstall the cable covers. The hole size and quantity are for reference only. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 127 Step 5 Connect a ground cable to the UPS. If you do not ground the UPS as required, electromagnetic interference, electric shocks, or fire may occur. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 128 Figure 3-70 Grounding Step 6 Connect the bypass input power cables. (Perform this step only when the mains input and bypass input use different power sources.) Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 129 Step 7 Connect the output power cables. After connecting the output power cables, if loads are not ready to be powered, insulate the terminals of the output power cables. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 130 UPS5000-E-(350 kVA-800 kVA) User Manual (50 kVA Power Modules) 3 Installation Figure 3-72 Connecting output power cables Step 8 Connect the mains input power cables. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 131 UPS5000-E-(350 kVA-800 kVA) User Manual (50 kVA Power Modules) 3 Installation Figure 3-73 Connecting the mains input power cables Step 9 Connect the battery cables. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 132 Take a battery string consisting of 40 batteries for example. The battery neutral wire is routed from the middle of positive and negative battery strings, each consisting of 20 batteries. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 133 Figure 3-76 Signal cables routed from the bottom The number and colors of signal cables in Figure 3-76 are for reference only. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 134: Routing Cables (800 Kva Ups)

    The figures are for reference only. For more information about the recommended cable cross-sectional area and quantity, refer to 3.1.3 Power Cables and site requirements. Figure 3-77 shows power cable terminals. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 135 Step 2 Remove the cable covers from the top of the cabinet, drill holes in the covers, attach grommet strips to the hole edges for protecting cables, and reinstall the cable covers. The hole size and quantity are for reference only. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 136 (Optional) If copper bar protective covers are installed for the bypass cabinet, remove the protective covers and then the connecting copper bars. The protective covers need to be reinstalled after the connecting copper bars are removed. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 137 UPS5000-E-(350 kVA-800 kVA) User Manual (50 kVA Power Modules) 3 Installation Figure 3-79 Removing the connecting copper bars Step 5 Connect a ground cable to the UPS. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 138  Connect the input power cables to the UPS before connecting power cables to customer equipment. Figure 3-80 Grounding Step 6 Connect the mains input power cables. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 139 Step 7 Connect the output power cables. After connecting the output power cables, if loads are not ready to be powered, insulate the terminals of the output power cables. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 140 Step 8 Connect the bypass input power cables. (Perform this step only when the mains input and bypass input use different power sources.) Figure 3-83 Connecting the bypass input power cables Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 141 Take a battery string consisting of 40 batteries for example. The battery neutral wire is routed from the middle of positive and negative battery strings, each consisting of 20 batteries. Figure 3-85 Neutral wire Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 142: Bottom Cable Routing

    After connecting cables, check that a certain clearance is reserved between the internal switch (if any) extension pole and power cables to avoid friction. 3.2.7.2 Bottom Cable Routing Context Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 143 Figure 3-87 Removing the bottom cable covers and drilling holes Step 3 Remove the rear cover from the bypass cabinet. You are advised to remove the side panel from the bypass cabinet before connecting cables. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 144 Figure 3-88 Grounding Step 6 Connect the bypass input power cables. (Perform this step only when the mains input and bypass input use different power sources.) Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 145 Step 7 Connect the output power cables. After connecting the output power cables, if loads are not ready to be powered, insulate the terminals of the output power cables. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 146 UPS5000-E-(350 kVA-800 kVA) User Manual (50 kVA Power Modules) 3 Installation Figure 3-90 Connecting the output power cables Step 8 Connect the mains input power cables. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 147 UPS5000-E-(350 kVA-800 kVA) User Manual (50 kVA Power Modules) 3 Installation Figure 3-91 Connecting the mains input power cables Step 9 Connect the battery cables. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 148 Take a battery string consisting of 40 batteries for example. The battery neutral wire is routed from the middle of positive and negative battery strings, each consisting of 20 batteries. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 149 Step 10 Route signal cables. Bind cables to the cabinet. Figure 3-94 shows the signal cables routed from the bottom of the cabinet. Do not bind signal cables and power cables together. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 150: Remote Epo

    (if any) extension pole and power cables to avoid friction. 3.2.8 Remote EPO  Huawei does not provide the EPO switch or cable. If the cable is required, the recommended cable is 22 AWG.  Equip the EPO switch with a protective cover to prevent misoperations, and cover the cable with protective tubing.
  • Page 151: Connecting Communications Cables

    Procedure Step 1 Connect the external network management device to the RS485 port. Step 2 Connect the network port on a PC to the FE port. ----End Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 152: Parallel System Installation

    1+1 parallel system. Figure 3-97 Conceptual diagram of a 1+1 parallel system Connect power cables according to port silk screen. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 153 Figure 3-98 Cable connections for a 1+1 parallel system (400 kVA UPS) (1) Mains input power (2) Bypass input power (3) Battery (4) Output power cables cables cables cables Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 154 The length and specifications of power cables on each UPS must be the same to achieve current equalization in bypass mode. The power cables include bypass input power cables and UPS output power cables. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 155 UPS5000-E-(350 kVA-800 kVA) User Manual (50 kVA Power Modules) 3 Installation Figure 3-100 Conceptual diagram of a dual-bus system Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 156 Figure 3-101 Cable connections for a dual-bus parallel system (400 kVA UPS) (1) Mains input power (2) Bypass input power (3) Battery (4) Output power cables cables cables cables Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 157: Connecting Signal Cables

    Connect the parallel ports on the UPSs over parallel cables to create a loop.  Figure 3-103 Figure 3-104 show the wiring principle for an N+X parallel system. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 158 Figure 3-104 Signal cable connections of N+X parallel system  BSC master and slave cables are required in a dual-bus parallel system. Figure 3-105 shows the cable connections for a dual-bus system containing twomaster systems. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 159: Installation Verification

    Figure 3-105 Connecting signal cables to a dual-bus system Connecting Other Signal Cables Connect signal cables for each UPS. 3.4 Installation Verification Table 3-11 lists check items. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 160 3. There is no foreign matter around switch terminals. 4. There is no foreign matter on the bottom plate of the cabinet. 5. There is no foreign matter on the rear module subrack. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 161 (1) Switches (2) Mains input wiring copper (3) Battery input wiring copper bar (4) Output wiring copper (5) Bypass input wiring (6) Rear of modules copper bar Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 162 Figure 3-107 Positions to be checked for foreign matter (800 kVA) (1) Cabinet top (2) Wiring terminal block (3) Switches (4) Cabinet bottom (5) Rear of modules Figure 3-108 Fill the holes with firestop putty Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 163 UPS5000-E-(350 kVA-800 kVA) User Manual (50 kVA Power Modules) 3 Installation Figure 3-109 Dustproof cover Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 164: User Interface

    Figure 4-1 Menu hierarchy 4.1.2 Initial Startup User interfaces displayed in this document correspond to the monitor display module (MDU) version V100R003C01SPC403 and are for reference only. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 165: Main Menu

    The LCD screen is divided into three parts: status bar, alarm bar and information area. Figure numerically labels functions of the default main screen, and Table 4-1 describes these functions. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 166 Table 4-2 Functions of common buttons Button Function Returns to the main screen. Scrolls the page down. Scrolls the page up. Returns to the upper-level menu. Logs a user out. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 167: System Info Screen

    Runn Info screen. On this screen, AC Output, UPS Load, Mains Input, and Bypass Input can be queried, as shown in Figure 4-6 Figure 4-7. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 168 On the System Info > Settings > CIM Param. > Basic Param. screen, if the Number of battery strings is not 0, the Battery Detailed Data is displayed on the Runn Info screen. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 169 AC output phase current AC output frequency Frequency (Hz) Power factor Proportion of output active power to output apparent power. UPS Load Figure 4-9 UPS Load screen Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 170 Phase current (A) Mains input phase current Mains input frequency Frequency (Hz) Power factor Proportion of the mains input active power to the mains input apparent power. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 171 Frequency (Hz) Bypass input frequency Proportion of the bypass input active power Power factor to the bypass input apparent power. Battery Status Figure 4-12 Battery Status screen Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 172 Time for which the UPS runs in bypass mode. Time for which the UPS runs in inverter Inv. runtime (h) mode. The value must be an integer. For example: Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 173 Humidity measured by the ambient temperature and humidity sensor. If the humid. sensor is not installed, NA is displayed. Mod. Cur. Eql. Data Figure 4-15 shows the Mod. Cur. Eql. Data screen. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 174 This screen details battery string data and single battery data in each battery string. The N in String N Battery Data should be less than or equal to 4. Figure 4-17 shows the Batt. String Data screen. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 175: Alarms Screen

    CIM and BIM. 4.1.4.3 Alarms Screen on the System Info screen to enter the Alarms screen. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 176 UPS5000-E-(350 kVA-800 kVA) User Manual (50 kVA Power Modules) 4 User Interface Figure 4-19 Alarms screen Active Alarms Figure 4-20 Active Alarms screen Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 177 If this selection is enabled, the buzzer is muted. If the buzzer is enabled, Buzzer Off is displayed on the operation screen. Figure 4-22 Buzzer Off screen Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 178: Settings Screen

    On the login screen, enter a preset user name and password, and tap to log in. The Settings screen is displayed, as shown in Figure 4-25 Figure 4-26. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 179 Figure 4-26 Settings screen 2 Basic Settings Set the date and time correctly. Incorrect time display in running and alarm information would lead to analysis errors during maintenance or repair. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 180 If the password complexity check is complexity enabled, the password is required to be a string of 6–20 characters and check contain at least two types of characters. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 181 01.01000000 − Automatic: The MDU automatically searches for available IP addresses in the connected network. Ensure that the MDU and PC are on the same network segment. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 182 None, Odd, and Even. Stop bit in the Modbus communication frame format. When the UPS is RS485 Stop connected over the serial port Modbus, set this parameter based on the Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 183 WiFi SSID When using the mobile app for site setup or inspection, set WiFi SSID after connecting a WiFi module over a USB port to identify the WiFi Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 184 The value for the UPS running mode can be Single (default) or Parallel. arallel Output The value for the system output frequency can be 50 Hz (default) or 60 Hz. frequenc y (Hz) Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 185 If this is set (kVA) incorrectly, the Module quantity mismatch alarm will be generated. Power Rated power module capacity. module Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 186 A cycle of 1 to 100 days can be set. The parameter is set to 30 days by cycle hiber. default. period (d) High An alarm is generated when the ambient temperature reaches or exceeds Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 187 LCD when the inverter cannot track the bypass frequency change. Normal power supply is not affected no matter whether this parameter is set to Enable or Disable. The default value is Disable. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 188 When the inverter capacitor current is lower than the current specified by detection this parameter, the power module determines that the inverter capacitor is lower limit faulty and shuts down the inverter. If Capacitor failure detection lower Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 189 Specifies the rack air filter maintenance interval. If it is set to 0, there is no maintenanc reminder. The value range is 0 to 365. The default value is 0. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 190 EPO switch is triggered. This function is enabled by default. Figure 4-38 Advanced Param. screen 6 UPS model should be set by professional technical personnel of Huawei or personnel authorized by Huawei. Item Description Lightload BPM cur.
  • Page 191 1/8 of the normal delay to accelerate the power module start delay (s) transfer and prevent battery overdischarge. Intra-rack power module Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 192 This parameter can be adjusted based on site requirements. If Output (Hz/s) freq. track rate (Hz/s) is slow, the inverter frequency is different from the bypass frequency when the bypass frequency changes. If output is Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 193 NOTE Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 194 Enable. upon BPM overtemp. Battery Parameter Settings Battery parameter settings impact battery maintenance, battery lifespan, and UPS discharge time. When you set battery parameters, note the following: Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 195 0.05–0.15, and is 0.1 by default. (C10) Cell float The float voltage value can be 2.23–2.30 V/cell, and is 2.25 V/cell by default. voltage Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 196 Scheduled equalized charging interval. The value range of Equalized charging protection interval is 0 to 15 and the default value is 7. The value range of Scheduled Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 197 3° C) is generated. The Undertemp. thresh. (° C) alarm thresh. can be set from –20° C to +5° C and the default value is Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 198 EOD (V/cell), Dis. cur. (V/cell) to 1.60. These values are calculated in real time based 0.5C EOD (V/cell), and on the discharge currents. Dis. cur. 1.0C EOD (V/cell) Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 199 Single batt. dis. voltage deviation alarm thres. (%) is 10 to 30 and the deviation default value is 20. alarm thres. The calculation formula is (Charge/Discharge voltage – Average voltage)/Average voltage x 100%. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 200 Dry contact extended card (MUE07A): provides two routes of input signals and one route of output signals. Set the dry contact parameters, as shown in Figure 4-48 Figure 4-54. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 201 Enable or disable BCB connection detection. connection [OL] Batter Enable or disable battery circuit breaker monitoring. breaker [STA] PDC output Enable or disable PDC output circuit breaker monitoring. breaker [OUT] Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 202 Set this parameter to determine whether the port is used to T switch detect the status of the PDU input surge protector, or system output function switch. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 203 MUS05A DO_3 Action card. MUS05A Control the status of the DO_4 dry contact on the MUS05A dry contact DO_4 Action card. Figure 4-51 Dry Contacts screen 4 Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 204 Corresponds to signal of the output dry contact DO_3 on the MUS05A. DO_3 MUS05A Corresponds to signal of the output dry contact DO_4 on the MUS05A. DO_4 Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 205 Corresponds to signal of the output dry contact DO_4 on the MUE07A. DO_4 Corresponds to signal of the output dry contact DO_5 on the MUE07A. MUE07A DO_5 Figure 4-54 Dry Contacts screen 7 Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 206 On the System Info > Settings > CIM Param. > Basic Param. screen, if Number of battery strings is 0, the Batt. String Config is not displayed on the CIM Param. screen.  Figure 4-56 Figure 4-57 show the Basic Param. screen. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 207 0 to 4. The default value is 0. strings Specifies the number of batteries in a battery string. The value range is 0 to Batteries 300. The default value is 0. in a single Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 208 The default value is 1.  Figure 4-59 shows the battery string config screen. On this screen, the CIM No. and BIM No. can be set under each battery string. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 209: Maintenance Screen

    USB Operations, Inv. ON, and Inv. OFF. If a user is not currently logged in, a dialog box will display for entering a user name and password. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 210 On the System Info > Settings > Advanced Param. screen, when Bus Capa. Life is set to Enable, the Bus Capa. Life is displayed on the Maintenance screen. Battery Maint. Screen Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 211 Fully discharge batteries. A deep discharge Capacity Test test is conducted to obtain the battery discharge performance data. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 212 Use the LCD to start and shut down the inverter. Before the inverter starts, the system asks for confirmation to prevent misoperations. Figure 4-66 shows the Inv. ON screen, and Figure 4-67 shows the Inv. OFF screen. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 213 The Inv. ON screen allows you to start the inverter Inv. ON manually. The Inv. OFF screen allows you to shut down the inverter Inv. OFF manually. ECM Switchover Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 214 ECM. Figure 4-68 ECM switchover Screen Calib. Menu Calibrate the screen, as shown in Figure 4-69. Figure 4-69 Screen Calib. screen Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 215 Bus capacitor life forecast If the service life of a capacitor is about to end, that is, Module X bus capacitor life (y) is less than 1.0, contact Huawei technical support to replace the power module. Issue 05 (2018-01-08) Huawei Proprietary and Confidential...
  • Page 216: About Screen

    On the main screen, tap System Status. On the System Status to view the mains input, bypass input, load, and battery information, as shown in Figure 4-73. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 217: Common Functions Screen

    Figure 4-74 Figure 4-75. Figure 4-74 Common Functions screen 1 Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 218: Webui

    Step 1 Open the browser and choose Tools > Internet Options. Step 2 On the Advanced tab page, ensure that Use TLS 1.0, and Use TLS 1.1 are selected and click OK, as shown in Figure 4-76. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 219 (historical alarms, logs, e-labels, and fault data) exporting, parameter (system parameters and battery parameters) setting, system control (startup, shutdown, troubleshooting, runtime clearing, and battery management), system Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 220: Monitoring Page

    After a user logs in to the WebUI, the Monitoring page is displayed by default. Figure 4-77 numerically labels Monitoring page details and Table 4-5 describes these details. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 221: Active Alarms Page

    The Active Alarms page is displayed by default. Information Displays system monitoring information. area 4.2.2.1 Active Alarms Page The Active Alarms page details active alarms, as shown in Figure 4-78. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 222: Real-Time Data Page

    4.2.2.3 Param. Settings Page Set basic parameters, advanced parameters, input parameters, output parameters, bypass parameters, battery parameters, and dry contacts on the Param. Settings page, as shown in Figure 4-80. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 223: Comm. Config. Page

    Figure 4-81 Comm. Config. page 4.2.2.5 CIM Parameters Open the CIM Param. Screen to set basic parameters, advanced parameters, and battery string configurations, as shown in Figure 4-82. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 224: Control Page

    On the homepage, click the Query tab to open the Historical Alarms page for querying historical alarms based on severity, generation time, and clear time, as shown in Figure 4-84. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 225: Logs

    Figure 4-85. Historical logs can be exported but not queried. Figure 4-85 Logs 4.2.4 Config. 4.2.4.1 User Management On the home page, choose Config. > User Mgmt. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 226: Site Config. Page

    If the password complexity check is enabled, the user password is required to be a string of 6–20 characters and contain at least two types of characters. 4.2.4.2 Site Config. Page On the home page, choose Config. > Site Config. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 227 ModbusTCP Certificate Management: ModbusTCP supports the Transport Layer Security (TLS) secure protocol for encrypted transmission and implements access authentication through the bidirectional certificate. Customers can replace the UPS certificate with the certificate trusted by them. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 228: Rccmd

    Enable upon first login. After you submit the setting, the page refreshes. The controls such as SSL Encrypted Transmission and Event Configuration will be displayed on the page, as shown in Figure 4-89. Figure 4-88 RCCMD function disabled Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 229 Disable, the RCCMD certificate controls will not be displayed on the page, as shown in Figure 4-91. If SSL Encrypted Transmission is set to Disable, a message indicating there is a risk will be displayed. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 230 The MDU supports 17 alarm events, and a maximum of 50 jobs can be added for each event, as shown in Figure 4-92. Figure 4-92 shows the buttons on the Event Configuration page, Table 4-6 describes these buttons. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 231 You can delete all jobs of the event by clicking this button. Figure 4-93 shows the buttons after one event is expanded and Table 4-7 describes these buttons. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 232 When adding a job, the job types to be selected are: RCCMD Shutdown, RCCMD Message, RCCMD Execute, and RCCMD TRAP. RCCMD Shutdown is selected by default. For different job types, you need to enter different contents. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 233 RCCMD Message: Specify the RCCMD client IP address, port, and message to be conveyed. The RCCMD client will receive the message. For example, enter "This is a test message". Figure 4-95 RCCMD message Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 234 UPS input voltage value (for example, single-phase: 220 V; three-phase A: 220 V, B: 220 V, C: 220 V). Table 4-8 lists the signal names that can be entered. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 235 #STATUS UPS status #RUNTIME UPS operating time minutes #BATTVOLT Battery voltage #INFREQ Input frequency #BYPASSINFREQ Bypass input frequency #OUTFREQ Output frequency #CNT_PF Power supply failure times Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 236 After the certificate is uploaded successfully, click Submit. The WebUI of the MDU will restart, and the uploaded certificate will be used for communication. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 237: Managing The Ups By Using The Nms Complying With Rfc1628 Standard

    MIB file which allows the third-party NMS to manage the UPS remotely. Figure 4-99 Download the MIB The UPS-RFC1628-MIB has more alarms than RFC1628. Download the UPS-RFC1628-MIB before using. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 238: Maint. Page

    Non-professional engineers should exercise caution when operating the maintenance page. On the homepage, click the Maint. tab to open the Maint. page. Maintenance functions include calibration, commissioning variables, upgrade, and downloading data. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 239 UPS5000-E-(350 kVA-800 kVA) User Manual (50 kVA Power Modules) 4 User Interface Figure 4-101 Calib. page Figure 4-102 Commissioning Var. page Figure 4-103 Upgrade page Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 240: Protecting The Server By Using The Rccmd Software

    Configures and saves the address and port for receiving the shutdown command, and the message sending mechanism. For the method of installing the RCCMD client, see the manual related to the RCCMD. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 241: Rccmd Event Shutdown And Message Sending

    RCCMD client at the same time to keep them the same. Enter the message to be sent and set the message sending mechanism. For example, set it to Immediately, once. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 242: Ups Alive Check Function

    CS121/UPSMAN Traps. If by polling CS121/UPSMAN every x seconds... is selected as the method of detecting heartbeats, set the detection method. The default interval is 1800s and detection is performed 100 times, as shown in Figure 4-108. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 243 User Manual (50 kVA Power Modules) 4 User Interface Figure 4-108 Heartbeat detecting mode on the RCCMD client You can also manually detect heartbeat by clicking Run alive check now..Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 244 UPS5000-E-(350 kVA-800 kVA) User Manual (50 kVA Power Modules) 4 User Interface Figure 4-109 Detecting heartbeat manually Figure 4-110 Detecting heartbeat manually and successfully ----End Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 245: Operations

    Step 1 Close the upstream bypass and mains input switches. Step 2 (Full configuration model) Close the UPS bypass input switch, mains input switch, and output switch. After the UPS is powered on, initialization begins. The MDU displays the Huawei logo and an initialization progress bar. ----End 5.1.2 Starting the Inverter...
  • Page 246: Initial Startup

    Set Output frequency correctly; otherwise, loads may be affected and the UPS may not work properly. Battery parameter settings are critical to battery maintenance, battery lifespan, and UPS discharge time. When you set battery parameters, note the following: Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 247 When no battery string is shared, the battery capacity of each UPS is the capacity of battery strings connected to the single UPS. If you are not sure how to determine the battery capacity, contact Huawei technical support. ...
  • Page 248 Step 3 View the system running diagram on the MDU to check that the UPS is working in bypass mode. ----End Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 249 Step 3 Open the Service Expert app on the mobile phone. Step 4 On the home screen of the app, tap Power-on password activation to access the Set Startup screen. After setting parameters, tap Login. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 250 Same as the user name and password of WebUI accounts. Step 5 After login, tap Power-on password activation on the screen. In the displayed dialog box, tap OK to start the UPS. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 251 Step 2 On the home screen of the app, tap Startup to access the Set Startup screen. Step 3 Set Site and Device Type as required, and tap Offline Activation. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 252 The values of the BarCode and Codes in the figure are for reference only. The actual values prevail. Step 5 Enter BarCode and Codes obtained from the MDU on the Offline Activation screen. Tap Generate PWD to generate a startup password. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 253: Non-Initial Startup

    Step 2 In the displayed login screen, enter the user name and password. Step 3 In the displayed dialog box, tap Yes to start the inverter. ----End Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 254 Figure 5-8 Logging in to the WebUI Step 5 On the home page of the WebUI, choose Monitoring > Control, click Inv. ON, and confirm the operation to start the inverter. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 255: Powering On Loads

    A BCB box is installed. Procedure Step 1 On the Settings > Dry Contacts screen, set MUE05A connection to Enable, and set BCB connection [OL] and Battery breaker [STA] to Enable. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 256: Shutting Down And Powering Off The Ups

    If no user is logged in, enter a user name and password, and tap on the login screen displayed. In the displayed dialog box, tap Yes to shut down the inverter. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 257 After the inverter shuts down, the UPS works in bypass mode if the bypass is normal, as shown in Figure 5-13; the UPS supplies no power and the loads power off if the bypass is abnormal, as shown in Figure 5-14. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 258 Open the internal mains input switch, bypass input switch, and output switch. Open the external mains and bypass input switches. Step 5 For a UPS in standard configuration, open the external mains and bypass input switches. ----End Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 259: Starting The Ups In Battery Mode

    Number of cells), the batteries are connected properly. Step 4 Press and hold down the BATT START button on the bypass module for at least 2 seconds. The system automatically enters the battery cold start status. The LCD displays the Huawei logo and an initialization progress bar.
  • Page 260 Step 3 Set Working mode to ECO. Information indicating that the UPS works in ECO mode is displayed on the LCD. Figure 5-16 Setting ECO mode Step 4 Manually start the inverter. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 261: Testing Batteries

    If the inverter is not started, the UPS may be disconnected. Figure 5-17 System Status screen ----End 5.6 Testing Batteries 5.6.1 Forced Equalized Charging Test Context Before a forced equalized charging test, ensure that: Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 262 The forced equalized charging test duration reaches the forced equalized charging protection time (12–24 h, 18 h by default).  The UPS generates a battery overtemperature, overvoltage, or overcurrent alarm.  An alarm is generated. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 263: Shallow Discharge Test

    Step 2 On the Maintenance screen, tap Battery Maint. Step 3 Tap Start next to Shallow Dis. Test to start a shallow discharge test. Figure 5-20 Starting a shallow discharge test Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 264: Capacity Test

    . The Maintenance screen is displayed. Step 2 On the Maintenance screen, tap Battery Maint.. Step 3 Tap Start next to Capacity Test to start a capacity test. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 265: Test Data Download

    Step 2 On the main screen of the LCD, choose System Info. Tap . The Maintenance screen is displayed. Step 3 Choose USB Operations > Export Logs, and select a log download path. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 266: Download Over The Webui

    Step 1 Log in to the WebUI. Step 2 Choose Query > Logs, select logs from the Log drop-down list box, then click Export to export logs. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 267: Transferring To Maintenance Bypass Mode

    Figure 5-27 Figure 5-28. The Maint. breaker closed alarm is displayed in the alarm list, as shown in Figure 5-29. The UPS transfers to maintenance bypass mode. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 268 Figure 5-25 Locked maintenance bypass switch (400 kVA UPS and 500 kVA UPS) Figure 5-26 Locked maintenance bypass switch (600 kVA UPS) Figure 5-27 Closing the maintenance bypass switch (400 kVA UPS in full configuration) Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 269 Figure 5-29 Maint. breaker closed alarm After the UPS transfers to maintenance bypass mode, the Maint. breaker closed and Bypass mode alarms are displayed on the LCD. ----End Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 270: Transferring From Maintenance Bypass Mode To Normal Mode

    LCD or WebUI. Figure 5-30 Opening the maintenance bypass switch (400 kVA UPS in full configuration) Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 271: Performing Epo

    Press the EPO button connected to the dry contact card or remove the 4-pin terminal from the EPO port on the dry contact card. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 272: Clearing The Epo State

    Figure 5-33 Clearing faults  On the WebUI Choose Monitoring > Control > System Commands and Tests and click Clear Fault. The EPO alarm is cleared successfully. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 273: Exporting Data

    CIM version  Fault Data This topic describes how to export historical alarms. Procedure Step 1 Choose Query > Historical Alarms, and set Severity, Generated, and Cleared. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 274: Setting Hibernation Mode

    This improves the system efficiency, reduces power consumption, and increases the power module service life. Use the LCD or WebUI to set hibernation mode. Before starting hibernation mode: Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 275: Lcd

    Figure 5-37 Hibernation parameters on the LCD Step 3 On the LCD, set Paral. sys. hibernate to Enable. A confirmation message is displayed, as shown in Figure 5-38. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 276: Webui

    Step 1 On the login page, enter a user name and password, and click Login. Step 2 Choose Monitoring > Param. Settings > Advanced Param., as shown in Figure 5-39. Figure 5-39 Hibernation parameters on the WebUI Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 277 Click Submit after you set the parameter on the WebUI. Step 4 Set Module cycle hiber. period (d) to an integer ranging from 1 to 100. The default value is ----End Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 278: Routine Maintenance

    Power grid  Input voltage: 380 V AC, 400  If the input voltage is environment V AC, or 415 V AC (line abnormal, check the power grid Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 279: Quarterly Maintenance

    The insulation layer of  Replace the cables. (between the UPS and the cables is intact and terminals  Secure the output are free from black marks Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 280: Battery Maintenance

    Before installing batteries, read through the battery user manuals and pay attention to safety precautions and connection methods provided by battery manufacture. When installing and maintaining batteries, pay attention to the following points: Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 281: Precautions For Battery Maintenance

    (2.35 V/cell ± 1%) x number of and the battery input terminals battery cells at the UPS side is greater than Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 282: Quarterly Maintenance

    3. If the fault persists, contact Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 283: Annual Maintenance

    (A torque wrench is used for checking the torque. After checking that the battery screws meet the requirements, mark the screws for later check.) Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 284: Troubleshooting

    Close the battery switch and charge batteries until each battery has a voltage greater than the EOD voltage and 11.3 V/cell. For details about how to rectify common faults, see Table 7-1. If any unmentioned faults occur, see the alarm list chapter, or contact Huawei technical support. Table 7-1 Troubleshooting Case Symptom Possible Cause...
  • Page 285 The bypass thyristor is Replace the bypass bypass and the Fault indicator is damaged. module. is not The bypass module Reduce the load, or normal. experiences improve ventilation. overtemperature. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 286 UPS5000-E-(350 kVA-800 kVA) User Manual (50 kVA Power Modules) 7 Troubleshooting For details about component replacement and maintenance involved in Troubleshooting and Alarm List, consult Huawei maintenance engineers. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 287: Technical Specifications

    1000 V AC/630 0K-SM A/3P UPS5000-E-40 1000 V AC/630 1000 V AC/800 1000 V AC/630 1000 V AC/630 0K-FM A/3P A/3P A/3P A/3P UPS5000-E-50 1000 V AC/800 0K-SM A/3P Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 288: Environment Parameters

    For details, see the IEC62040-3. 8.4 Safety Regulations and EMC Safety and 400 kVA 500 kVA 600 kVA 800 kVA Safety EN62040-1: 2013 regulations IEC62040-1: 2013 YD/T2165-2010 EN62040-2 IEC62040-2 Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 289: Mains Input Electrical Specifications

    400 kVA 500 kVA 600 kVA 800 kVA Input system Three-phase, four-wire, and PE Rated input 380 V AC, 400 V AC, or 415 V AC (line voltage) Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 290: Battery Specifications

     In normal mode, the mains frequency is synchronous with the bypass input frequency.  In battery mode, the frequency is 50 Hz or 60 Hz (tolerance Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 291: System Electrical Specifications

    8.9 System Electrical Specifications Item 400 kVA 500 kVA 600 kVA 800 kVA Redundancy The auxiliary power supplies, centralized controllers, and parallel signals design use redundancy design. Supported Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 292: A (Optional) Tn-C System Application

    600 kVA UPS.  The following cable connections are for reference only. Figure A-1 Short-circuiting the input N and PE (600 kVA UPS) Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 293 Figure A-2 Short-circuiting the input N and PE (800 kVA UPS) Table A-1 Recommended cross-sectional areas for cables Model Current (A) Recommended Cross-Sectional Area 400kVA 710.8 500kVA 888.5 600kVA 1066.2 800kVA 1421.6 Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 294: B Menu Hierarchy

    Total Runtime Environment Data Alarms Active Alarms Historical Alarms Buzzer Off Clear Faults Settings Basic Communication Basic Param. Advanced Param. Input Param. Output Param. Bypass Param. Battery Param. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 295 ECM Switchover Screen Calib. CIM Maint. About Model Manufacturer Monitoring Version Power Version Version Info Common AC Output Phase voltage Functions Line voltage Phase current Frequency Power factor Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 296: Menus On The Webui

    B.2 Menus on the WebUI Level–1 Level–2 Level–3 Level–4 Menu Level–5 Menu Menu Menu Menu Monitorin Active Alarms Real-time Input Phase voltage Data Line voltage Current Power factor Frequency Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 297 Reactive power System active power System apparent power System reactive power Battery Voltage Current Bus voltage Battery temperature Backup time Remaining capacity Environment Data Ambient temperature Ambient humidity Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 298 Power factor Load ratio Crest factor Battery String Param. Basic Param. Single/Parallel Settings Voltage level Output frequency Battery capacity Number of cells Advanced System capacity Param. Power module Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 299 Capacitor failure detection Capacitor failure detection upper limit Capacitor failure detection lower limit Input cur. limiting Input cur. limiting ratio No-load output shows zero Current equal. detection Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 300 Inter-rack power module start delay Input adaptability Output Param. Output volt. adjustment Outp. transf. interrupt time Self-load output cur. ratio Output interruption transfer time Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 301 Automatic equalized charging Forced equalized charging protection time Equalized charging protection interval Scheduled equalized charging interval Float volt. temp. comp. Float volt. temp. comp. coef. Max batt. dis.time Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 302 Intelligent hibernation Class 1 grid hiber. time Class 2 grid hiber. time Intelligent hibernation Single batt. float chg. voltage deviation alarm thres. Single batt. dis. voltage deviation Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 303 MUE06A connection MUS05A DO_1 Action MUS05A DO_2 Action MUS05A DO_3 Action MUS05A DO_4 Action MUE07A DO_1 Action MUE07A DO_2 Action MUE07A DO_3 Action MUE07A DO_4 Action Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 304 Start addr. of batt. Temperature temp. sensor Sensor Settings Batt. temp. sensors Ambient Start address of Temperature ambient temperature and Humidity and humidity Sensor Settings sensors Ambient temperature and Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 305 Commands and Inv. OFF Tests Clear Fault Bypass runtime (Clear) Inv. runtime (Clear) Forced equalized charging (Start, Stop) Shallow discharge test (Start, Stop) Capacity Test (Start, Stop) Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 306 Time zone System Date Date (Local) and Time Time (Local) System Name Information Location Contact information SNMP SNMP version SNMP port SNMP Trap Trap addr. Trap port Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 307 Configure Alarm Email Notification Email Address Language Alarm Severity Scheduled Notifi. ModbusTCP Upload Certificate Password Management Confirm password ModbusTCP Upload CA Certificate Management ModbusTCP Authentication Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 308 Ph. B output volt. Ph. C output volt. Module Ph. A input volt. Ph. B input volt. Ph. C input volt. Ph. A input cur. Ph. B input cur. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 309 Inv. ph. A induc. cur. Inv. ph. B induc. cur. Inv. ph. C induc. cur. BPM ph. A input volt. BPM ph. B input volt. BPM ph. C input volt. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 310 5 data Module Rec. SW commissioning var. 0 data Rec. SW commissioning var. 1 data Rec. SW commissioning var. 2 data Rec. SW commissioning var. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 311 ECM SW commissioning var. 1 data ECM SW commissioning var. 2 data ECM SW commissioning var. 3 data ECM SW commissioning var. 4 data ECM SW commissioning var. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 312 User Manual (50 kVA Power Modules) B Menu Hierarchy Level–1 Level–2 Level–3 Level–4 Menu Level–5 Menu Menu Menu Menu 5 data Upgrade Upgrade UPS Software Download Download Fault Data CIM version E-Label Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 313: C Alarm List

    0001-3 The mains is Check the mains. not normal. 0004-1 Mains ph. Minor Cable Verify the cable connections. Reversed connections are incorrect. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 314 Bypass The phase Check whether the cable phase 0011-1 Minor phase sequence of sequence is correct using a reversed multimeter. If no multimeter is Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 315 Minor  parameters are correctly set. overvoltage configure d number 2. If they are correctly set, certain batteries may be faulty. batteries 3. Check whether the battery Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 316 Replace the board. 1. Check the battery voltage.  0032-1 Battery Critical overvoltage battery 2. Check that the configured Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 317 2. Check whether the fans are functioning properly. Replace functionin the power module if the fans are faulty. properly.  The air channel Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 318 1. Rectify the fault and check  0061-2 Inverter Minor The I2C whether the alarm is cleared. alarm bus is not 2. If the alarm is generated again, Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 319 1. Check that there is no overload. Output  The load 0566-1 Minor overload 2. Check that the module power is excessive. not derated due to a fan fault. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 320 3. Replace the ECM. disconnec ted or short-circ uited.  Only one rack works in a parallel system.  An ECM is faulty. Replace the inter-rack parallel 0583-4 inter-rack Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 321 0087-1 System Warning Check the reason why the transfer-to- neighboring neighboring UPS transfers to Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 322 The running status is displayed. See disabled disabled. details about how to handle other alarms. 0337 Critical The bypass The running status is displayed. No bypass input circuit further measures are required. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 323  configure d number redundant racks is incorrect. 1. Reduce the load. 0095-1 Insuffi. Minor  The load redundancy 2. Decrease the configured number Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 324 OFF. rack meet the length requirements.  3. Rectify any bypass SCR length of open-circuit. the bypass input or output cables is incorrect. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 325 2. After maintenance, open the maintenance circuit breaker and then start the inverter. 0380 Warning The inverter Wait until the inverter self-check is self-check is in complete. self-check. Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 326: D Acronyms And Abbreviations

    BBB-BOX Conformite Europeenne control module digital signal processing economic control operation emergency power off energy control module end of discharge International Electrotechnical Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 327 Protocol total distortion of the input current THDi waveform THDv total harmonic distortion of output voltage uninterruptible power system Universal Serial Bus valve-regulated lead acid battery VRLA Issue 05 (2018-01-08) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.

Table of Contents