Huawei UPS5000-E-400K-SM Quick Manual

Hide thumbs Also See for UPS5000-E-400K-SM:

Advertisement

Quick Links

UPS5000-E-(350 kVA-500 kVA)
Quick Guide (50 kVA Power Modules)
Issue: 11
Part Number: 31507657
Date: 2022-12-30
1
Overview
UPS Model
UPS5000-E-400K-SM
UPS5000-E-400K-FM
UPS5000-E-500K-SM
UPS5000-E-500K-FM
The figures use the UPS in full configuration as an example. The UPS in standard
configuration does not have the mains input switch, output switch, or bypass input switch.
UPS5000-E-400K-SM/FM
(1) Power modules (2) Control module
(5) Bypass module (6) Mains input switch (7) Output switch
Weight
670 kg
710 kg
810 kg
830 kg
(3) Power distribution
module cover
Copyright © Huawei Digital Power Technologies Co., Ltd. 2022.
1
All rights reserved.
Dimensions (H x W x D)
2000 mm x 1200 mm x 850 mm
UPS5000-E-500K-SM/FM
(4) Maintenance bypass
switch
(8) Bypass input switch

Advertisement

Table of Contents
loading

Summary of Contents for Huawei UPS5000-E-400K-SM

  • Page 1 (3) Power distribution (4) Maintenance bypass (1) Power modules (2) Control module module cover switch (5) Bypass module (6) Mains input switch (7) Output switch (8) Bypass input switch Copyright © Huawei Digital Power Technologies Co., Ltd. 2022. All rights reserved.
  • Page 2: Installing The Ups

    UPS faults are beyond the warranty scope. 4. This document describes how to install a single UPS. For details about how to install parallel systems, contact Huawei technical support. Installing the UPS Determining the UPS Installation Position The UPS can be installed on channel steels or on the ground.
  • Page 3 Securing the UPS • Floor mounting: Secure the cabinet to the ground by using eight M12x60 expansion bolts. • Steel channel mounting: Secure the cabinet to steel channels by using eight M12x60 common bolts. (1) Cabinet mounting holes (ground installation mode) (2) Cabinet mounting holes (channel steel installation mode) Installing the Front, Rear, Left, and Right Anchor Baffle Plates...
  • Page 4: Connecting Cables

    Connecting Cables 1. This document describes cable routing by removing the top cover when there are two mains inputs. 2. In the case of single mains, you do not need to connect bypass input power cables and remove short-circuit copper bars. UPS Cable Connection Reference •...
  • Page 5 3. Remove the rear cover from the bypass cabinet, and then remove the connecting copper bars between mains input terminals and bypass input terminals. (If the mains input and bypass input share a power source, skip this step.) UPS5000-E-400K-SM/FM UPS5000-E-500K-SM/FM...
  • Page 6 4. Connect the ground cable to the UPS. 5. Connect mains input power cables. 7. Connect bypass input power cables. 6. Connect output power cables.
  • Page 7 8. Connect battery cables. Route a neutral wire from the middle of the positive and negative battery strings. Take a battery string consisting of 40 batteries as an example. A neutral wire is routed from the middle of positive and negative battery strings, each consisting of 20 batteries.
  • Page 8: Installation Verification

    Installation Verification 1. Check that there is no foreign matter in the cabinet. (1) Switches (2) Mains input wiring copper bars (3) Battery input wiring copper bars (4) Output wiring copper bars (5) Bypass input wiring copper bars (6) Cabinet rear 2.
  • Page 9: Powering On And Starting The Ups

    Close the upstream bypass and mains input switches. (Full configuration model) Close the UPS bypass input switch, output switch, and mains input switch. After the UPS is powered on, initialization begins. The MDU displays the Huawei logo and an initialization progress bar.
  • Page 10: Initial Startup

    Initial Startup 1. Obtain the startup password through the app. After the application is approved, enter the password on the service authorization screen of the device to complete device authorization. Technical support engineers can obtain the service authorization code through the app. For details, see the Data Center Facility Deployment Guide 2.
  • Page 11: Shutting Down The Ups

    System User LCD Preset Password WebUI Preset Password admin (system administrator) 000001 Changeme operator (common user) 000001 Changeme Powering On Loads 1. After the inverter starts, the UPS works in normal mode. The Bypass mode alarm disappears from the MDU. 2.
  • Page 12 Huawei Digital Power Technologies Co., Ltd. Huawei Digital Power Antuoshan Headquarters Futian, Shenzhen 518043 People’s Republic of China www.huawei.com...