UPS5000-E-(350 kVA-800 kVA)
User Manual (50 kVA Power Modules)
Figure 5-32 EPO ports
After you press the EPO button, the EPO and No power supplied alarms are displayed on the
LCD.

5.10 Clearing the EPO State

Procedure
Step 1 Clear the EPO state. Ensure that the EPO button connected to the dry contact is not in the
EPO state.
Step 2 Clear the EPO alarm.
Issue 05 (2018-01-08)
On the LCD
On the LCD, choose System Info > Alarms and tap Clear Faults. In the displayed
dialog box, tap Yes. The EPO alarm is cleared successfully.
Figure 5-33 Clearing faults
On the WebUI
Choose Monitoring > Control > System Commands and Tests and click Clear Fault.
The EPO alarm is cleared successfully.