Huawei UPS5000-E-400K-SM User Manual page 320

Hide thumbs Also See for UPS5000-E-400K-SM:
Table of Contents

Advertisement

UPS5000-E-(350 kVA-800 kVA)
User Manual (50 kVA Power Modules)
Alarm
ID
(Alarm
ID-Caus
e ID)
0570-4
0583-1
0583-4
Issue 05 (2018-01-08)
Alarm
Severit
Name
y
BPM
Critical
module
abnormal
Inter-rack
Critical
par. cable
abnormal
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Cause
Solution
Derating
3. If the alarm persists, replace the
reduces
power module.
the rated
system
power.
The
module is
damaged.
1. Check the bypass fan and air
The
channel. If the fan is faulty,
bypass
replace it.
fan is not
functionin
2. Check that the ambient
g
temperature has not exceeded
properly,
40° C.
or the air
3. Check that there is no overload.
channel is
blocked.
The
ambient
temperatu
re exceeds
the upper
threshold.
The load
is
excessive.
1. Check the inter-rack parallel
The
system CAN bus.
inter-rack
parallel
2. Rectify the disconnection or
system
short-circuit fault.
CAN bus
3. Replace the ECM.
is
disconnec
ted or
short-circ
uited.
Only one
rack
works in a
parallel
system.
An ECM
is faulty.
The
Replace the inter-rack parallel
inter-rack
C Alarm List
311