Power Cables - Huawei UPS5000-E-400K-SM User Manual

Hide thumbs Also See for UPS5000-E-400K-SM:
Table of Contents

Advertisement

UPS5000-E-(350 kVA-800 kVA)
User Manual (50 kVA Power Modules)
Tools and Meters
Phillips screwdriver
(M3/M4/M5/M6/M
8)

3.1.3 Power Cables

Table 3-2
that the currents listed are measured at a rated voltage of 380 V.
Table 3-2 Recommended cross-sectional areas for power cables (350 kVA–550 kVA)
Item
Main
Mains input current
s
(A)
input
Recomme
L1
conn
nded
ector
L2
cross-secti
onal area
L3
2
(mm
)
N
Issue 05 (2018-01-08)
Insulated torque
wrench
(M6/M8/M12/M16)
Table 3-1
lists only the common tools for installation and cable connection. For more dedicated tools
required, see the corresponding component manuals. Prepare tools based on site requirements.
The UPS can generate large leakage currents. A circuit breaker that provides leakage
current protection is not recommended.
If multiple UPSs are to be connected in parallel, input and output power cables for each
UPS should have the same length and specifications.
The TN-C system is supported when the input N and PE are connected. For the connecting
method, see
A (Optional) TN-C System
and
Table 3-3
list the recommended cross-sectional areas for power cables. Note
350 kVA
622
2 x (4 x 185)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Heat shrink tubing
Application.
400 kVA
450 kVA
711
800
2 x (4 x 240)
3 x (4 x 185)
3 Installation
Insulated adjustable
wrench
500 kVA
550 kVA
889
977
3 x (4 x 185)
3 x (4 x 240)
55